Installation and commissioning manual
MDX-I/O M2M
Additional Input/Output module with Datalogger function
COMMISSIONING
20
5146 en - 2014.03 / a
LEROY-SOMER
19.30
: DO2 digital output source
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Format
: 16-bit
This parameter is used to select the source for
the digital output.
Any "bit" type parameter can be assigned. If
an unsuitable parameter is addressed, no
assignment is taken into account.
19.31
: DO3 digital output source
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Format
: 16-bit
This parameter is used to select the source for
the digital output.
Any "bit" type parameter can be assigned. If
an unsuitable parameter is addressed, no
assignment is taken into account.
19.32
: DI6 input destination
19.33
: DI7 input destination
19.34
: DI8 input destination
19.35
: DI9 input destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Format
: 16-bit
These parameters are used to select the
destination for the corresponding digital input.
Any "bit" type parameter can be assigned. If
an unsuitable parameter is addressed, no
assignment is taken into account.
19.36
: Sensor over-temperature
destination (KTY 84-130 or PT 100)
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Format
: 16-bit
To generate a trip, configure the destination
with a value likely to cause a user trip.
For example:
19.36
=
10.61
19.37
: Output relay 3 source
19.38
: Output relay 4 source
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Format
: 16-bit
These parameters are used to select the
source for output relays 3 and 4.
Any "bit" type parameter can be assigned. If
an unsuitable parameter is addressed, no
assignment is taken into account.
19.39
: Analog input AI4 level
Adjustment range : ±100.00%
Format
: 16-bit
Indicates as a percentage the signal level on
the differential analog input.
19.40
: Analog input 4 filter
Adjustment range : None (0), 4 ms (1),
8 ms (2), 16 ms (3),
32 ms (4).
Factory setting
: 8 ms (2)
Format
: 8-bit
None (0):
No filtering is applied to analog input AI4.
4 ms (1) to 32 ms (4):
Used to set the filter time constant applied to
analog input AI4.