5
LEROY-SOMER
InstallatIon and maIntenance
LSA 40 - 4 POLES
ALTERNATORS
4455 en - 10.2009 / a
TECHNICAL CHARACTERISTICS
2 -
Electrical characteristics
2.1 -
The PARTNER LSA 40 alternator is generator without sliprings
and revolving field brushes, wound as “2/3 pitch”; 12-wire, with
class H insulation and a field excitation system available in
either “SHUNT” or “AREP” version .
Interference suppression conforms with standard EN 55011,
group 1, class B.
Options
2.1.1 -
- Stator temperature detection probes.
- Space heaters.
Mechanical characteristics
2.2 -
- Steel frame
- End shields in cast iron
- Greasable ball bearings
- Mounting arrangement
md 35 :
single bearing with standard feet and SAE flanges/coupling
discs.
B 34 :
two-bearing with SAE flange and standard cylindrical shaft
extension.
- Drip-proof machine, self-cooled
Options
2.2.1 -
- Protection against harsh environmentsh.
- Air input filter, air output labyrinth cowling.
Alternators fitted with air inlet filters should be derated by 5%
(power).
To prevent excessive temperature rise caused by clogged
filters, it is advisable to fit the stator winding with thermal
sensors (PTC).
T1
T2
T3
T4
T5
T6
Va
ris
to
r
+
-
Field
STATOR : 12 wires (T1 to T12 identification)
Exciter
T7
T8
T9
T10
T11
T12
+
-
Armature
MAIN FIELD
R 220
Voltage reference
5+
6 -
Red
Black
SHUNT version
Aux. windings
Green
Yellow
Red
Black
T1
T2
T3
T4
T5
T6
Va
ris
to
r
+
-
Field
STATOR : 12 wires (T1 to T 12 identification)
Voltage reference
5+
Exciter
6-
T7
T8
T9
T10
T11
T12
+
-
Armature
MAIN FIELD
R 438
White
Blue
AREP version
Summary of Contents for LSA 40-4 POLE