Digidrive SK Technical Data
www.leroy-somer.com Issue Number: a
N
The total available current from the digital output plus the +24V output is 100mA
N
If the drives enable terminal is opened, the drives output is disabled and the motor will coast to a stop. The drive will not re-enable for 0.5s after the
enable terminal is closed again.
10.1 Drive reset
If the enable terminal is opened, the drive’s output is disabled and the motor will coast to a stop. The drive will not re-enable for 1.0s after the enable
terminal is closed again.
*
Following a drive trip, opening and closing the enable terminal will reset the drive. If the run forward or run reverse terminal is closed, the drive will
run straight away.
**
Following a drive trip and a reset via the stop/reset key, the enable, run forward or run reverse terminals will need to be opened and closed to allow
the drive to run. This ensures that the drive does not run when the stop/reset key is pressed.
The enable, run forward and run reverse terminals are level triggered apart from after a trip where they become edge triggered. See
*
and
**
above.
If the enable and run forward or enable and run reverse terminals are closed when the drive is powered up, the drive will run straight away up to a set
speed.
If both the run forward and run reverse terminals are closed, the drive will stop under the control of the ramp and stopping modes set in Pr
30
and
Pr
31
Provide fuse or other over-current protection in status relay circuit.
B1
Analog voltage output - Motor speed
Voltage output
0 to +10V
Scaling
0V represents 0Hz/rpm output
+10V represents the value in Pr
02
, maximum set speed
Maximum output current
5mA
Resolution
0.1%
Accuracy
±
5%
Update time
6ms
Protection
Tolerates continuous short circuit to 0V
B2
+24V output
Maximum output current
100mA
Protection
Tolerates continuous short circuit to 0V
Accuracy
±
15%
B3
Digital output - Zero speed
Voltage range
0 to +24V
Maximum output current
50mA at +24V (current source)
Output impedance
6.8k
Ω
Update time
1.5ms
Absolute maximum voltage range
+35V to -1V with respect to 0V common
B4
B5
B6
B7
Digital Input - Enable/Reset */**
Digital Input - Run Forward **
Digital Input - Run Reverse **
Digital Input - Local/Remote speed reference select (A1/A2)
Logic
Positive logic only
Voltage range
0 to +24V
Input impedance
6.8k
Ω
Sample time
1.5ms
Nominal threshold voltage
+10V
Absolute maximum voltage range
+35V to -18V with respect to 0V common
WARNING
NOTE
NOTE