Item
Message on
the LCD screen
7.7
7.8
7.9
7.10
7.11
7.12
Causes
The AVR is waiting for restart
command (for manual restart
mode only).
The internal temperature is
extremely high.
The internal temperature is
higher than the set point.
The AVR is overload.
The AVR is going to shut
down due to overload.
The AVR shuts itself down
due to running overload for
long time.
Solutions
Press
simultaneously once.
AVR will restart when it detects no fault.
- Check the AVR ventilation whether
anything is blocking.
- Disconnect some loads due to the AVR
is overload.
- Check the AVR ventilation whether
anything is blocking.
- Disconnect some loads due to the AVR
is overload.
Disconnect some loads until the load level
shows less than 100%.
Disconnect some loads until the load level
shows less than 100%.
Disconnect some loads until the load level
shows less than 100% and wait for 11
minutes. The AVR will restart
automatically (for automatic restart
mode) or press
simultaneously once (for manual restart
mode).
- 19 -