INSTALLATION AND OPERATION
4.1 Installation
Installation of the Wise33 / Wise MP33 series AVR must be done by professional technicians only.
Before installation, please read this userís guide carefully.
4.1.1 Transportation
You can move the Wise33 / Wise MP33 series AVR by forklift truck. In case that you have to lift it,
please consider
4.1.1.1
The AVR must be lifted upright at all time. Do not tilt.
4.1.1.2
Do not unpack the packaging until it reaches the installation site to protect the damages
during transportation.
4.1.2 Wire sizing
4.1.2.1
For safety and neatness, it is recommended to wire all wires in the conduit.
4.1.2.2
The wire size recommended in the table below is TIS no. 11-2531 PVC insulated copper wire
with conductor temperature 70 degree Celsius, 700 Volts, ambient temperature 40 degree
Celsius and maximum 3 wires wiring in the same conduit.
Note: The maximum length of the wires mentioned above is 5 meters. If you need to wire longer than 5
meters, the wire size must be increased. Contact us if you need assistance.
4.1.3 Wire the upper and lower decks (Type B only).
4.1.3.1
Wire PE (Earth) terminal of the upper deck to PE (Earth) terminal of the lower deck.
4.1.3.2
Wire N2 and N3 (Neutral) terminals of the lower deck to N of the CONNECT TERMINAL of the
upper deck.
4.1.3.3
Wire INPUT2 terminal of the lower deck to INPUT2 terminal of the upper deck.
4.1.3.4
Wire OUTPUT2 terminal of the lower deck to OUTPUT2 terminal of the upper deck.
4.1.3.5
Wire INPUT3 terminal of the lower deck to INPUT3 terminal of the upper deck.
4.1.3.6
Wire OUTPUT3 terminal of the lower deck to OUTPUT3 terminal of the upper deck.
4.1.4 Connect the OUTPUT terminal of the Wise33 / Wise MP33 series AVR to the loads as following:
N terminal connects to Neutral.
L1 terminal connects to R-phase or Line1 from loads.
L2 terminal connects to S-phase or Line2 from loads.
L3 terminal connects to T-phase or Line3 from loads.
4.1.5 Connect the INPUT terminal of the Wise33 / Wise MP33 series AVR to main electricity supply as
following:
PE terminal connects to Ground (Earth).
N terminal connects to Neutral.
L1 terminal connects to R-phase or Line1 of main electricity supply.
L2 terminal connects to S-phase or Line2 of main electricity supply.
L3 terminal connects to T-phase or Line3 of main electricity supply.
- 13 -
Rating
10kVA 15kVA 24kVA 30kVA 45kVA 60kVA 75kVA 90kVA 120kVA 150kVA 180kVA 210kVA 240kVA
Input wire (mm
2
)
4
6
10
16
25
35
50
2 x 35 2 x 50
2 x 50
3 x 70
3 x 70
3 x 70
Output wire (mm
2
)
4
6
10
16
25
35
50
2 x 35 2 x 50
2 x 50
2 x 70
3 x 70
3 x 70
Connect wire (mm
2
)
-
-
-
-
25
35
50
-
-
-
-
-
-
Earth wire (mm
2
)
2.5 to 4
4
4 to 6
6
10
10
16
25
25
35
35
35
35