Safety instructions
Safety instructions for the installation according to UL/CSA
2
12
Lenze ¯ BA_p500 ¯ 3.0
2.3
Safety instructions for the installation according to UL/CSA
Approval
Underwriter Laboratories (UL), UL 508 and CSA C22.2 No. 142−M1987 (UL File Number
E236341)
Ratings
¯
Input 24 V DC, max. 1.7 A
¯
Max. Surrounding temperature:
–
P500 7.0": 55 °C, in vertical (landscape or portrait) mounting position only at
relative humidity of 60 % RH with a linear derating to 30 °C at 90 % RH.
–
P500 10.4": 55 °C in vertical (landscape or portrait) mounting position only at a
relative humidity of 55 % RH with a linear derating to 40 °C at 90 % RH.
–
P500 15.0": 55 °C in vertical (landscape or portrait) mounting position only at a
relative humidity of 45 % RH with a linear derating to 40 °C at 90 % RH.
¯
These devices are intended for mounting in the outer surface of an enclosure,
Type 1, 4 and 4X indoor use only.
Warnings!
Field Wiring Markings
Wiring Terminal MSTB 2.5/3−STF−5.08:
¯ Use 60° or 60/75 °C copper wire only.
¯ AWG 18 ... 12 (0.82 ... 3.3 mm
2
)
¯ Torque 5...7 lb−in (0.5 ... 0.6 Nm)
Device
¯ For use in a pollution degree 2 and controlled environment only.
¯ For use on a Flat Surface of a Type 1, 4 and 4x Indoor Use Only
Enclosure
Optional filed bus module
¯ Use only together with appropriate cable connectors, provided with
screws for securement and secure connector to avoid loosening.