Technical data
Rated data
l
47
EDKRBS470R DE/EN/FR 10.0
4.2
Rated data
Electrical data
R
B
P
d
Q
B
U
max
[
W
]
[W]
[kWs]
[V
DC
]
ERBS020R03K2
20
3200
480.0
800
ERBS039R01K6
39
1640
246.0
ERBS082R780W
82
780
117.0
ERBS100R625W
100
625
94.0
ERBS180R350W
180
350
53.0
ERBS240R300W
240
300
45.0
ERBS470R150W
470
150
22.5
R
B
Resistance
P
d
Permanent power
Q
B
Heat quantity
U
max
Max. operating voltage
Temperatures
T
nom
T
TK
T
max
[°C]
On the surface
250
400
1000
On the clearance
edge
*)
120
200
300
T
nom
Maximum temperature for rated data
T
TK
Temperature at which the thermal contact is activated
T
max
Maximum temperature in the case of improper use
*)
Measured for air as the ambient medium (small coefficient of thermal
conductivity); if materials which heat up are located at the clearance edge
(greater coefficient of thermal conductivity), the temperature continues to
rise.