Technical data
General data and operating conditions
EDK94AZHN25 DE/EN/FR/ES/IT 2.2
33
H1_Daten−Maße_mm
General data
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
Approval
UR
UL 508C
Industrial Control Equipment Recognised
(file no. E132659) for USA
Protection of persons and equipment
Enclosure
EN 60529
IP00
Protective measures
Against short circuit
Mounting conditions
Mounting place
In the control cabinet
Mounting position
Vertically
Mounting clearances
Above/below
³
25 mm
To the sides
Side−by−side mounting without clearance
EMC
Noise emission
EN 61800−3
Conducted, category C2.
Noise immunity
EN 61800−3
Burst on mains cable:
2 kV/5 kHz
Burst on control cable:
2 kV/5 kHz
Surge on mains cable:
1 kV (1.2
m
s/50
m
s;
phase − phase)
2 kV (1.2
m
s/50
m
s;
phase − PE)