0.25 kW… 4.0 kW

V0004

SX03M

EN

 

Operating Instructions

smd 

- frequency inverter

-en1

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for ESMD112X2TXA

Page 1: ...0 25 kW 4 0 kW V0004 SX03M EN Operating Instructions smd frequency inverter en1 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 2: ...es of it s merchantability and fitness for a given purpose Lenze AC Tech Corporation assumes no responsibility for any errors that may appear in this manual All information given in this documentation...

Page 3: ...n 7 3 1 1 Dimensions and mounting 7 3 2 Electrical installation 8 3 2 1 Installation according to EMC requirements 8 3 2 2 Fuses cable cross sections 8 3 2 3 Connection diagram 9 3 2 4 Control termina...

Page 4: ...tely whether the items delivered match the accompanying papers Lenze does not accept any liability for deficiencies claimed subsequently Claim visible transport damage immediately to the forwarder vis...

Page 5: ...N 60204 must be observed Commissioning i e starting of operation as directed is only allowed when there is compliance with the EMC Directive 2004 108 EEC The drive controllers meet the requirements of...

Page 6: ...ntegrated controllers UL warnings are notes which apply to UL systems The documentation contains special information about UL Warnings Suitable for use on a circuit capable of delivering not more than...

Page 7: ...h leakage current 3 5 mA to PE Enclosure EN 60529 IP 20 Protection measures against short circuit earth fault overvoltage motor stalling motor overload Operation in public supply networks Limitation o...

Page 8: ...7 0 6 4 10 5 9 6 ESMD222X2SFA 2 2 21 0 9 5 8 7 14 3 13 1 ESMD371X2TXA 0 37 3 PE 230 240 V 180 V 0 264 V 0 50 60 Hz 48 Hz 0 62 Hz 0 2 7 2 4 2 2 3 6 3 3 ESMD751X2TXA 0 75 5 1 4 2 3 9 6 3 5 9 ESMD112X2TX...

Page 9: ...0 1 4 ESMD371X2TXA 93 84 146 128 17 83 0 5 ESMD751X2TXA 93 84 146 128 17 92 0 6 ESMD112X2TXA 93 84 146 128 17 141 1 2 ESMD152X2TXA ESMD222X2TXA 114 105 146 128 17 140 1 4 ESMD302X2TXA 114 105 146 128...

Page 10: ...A M16 A C16 A 15 A 2 5 14 ESMD152X2SFA ESMD302X2TXA M20 A C20 A 20 A 4 4 12 ESMD222X2SFA ESMD402X2TXA M25 A C25 A 25 A 6 4 10 1 Observe the applicable local regulations 2 Pulse current or universal cu...

Page 11: ...uit potentials are up to 240 VAC above earth ground Capacitors retain charge after power is removed Disconnect power and wait until the voltage between B and B is 0 VDC before servicing the drive Do n...

Page 12: ...Internal DC supply for setpoint potentiometer 10 V max 10 mA 20 Internal DC supply for digital inputs 12 V max 20 mA 28 Digital input Start Stop LOW Stop HIGH Run Enable R i 3 3 k E1 Digital input co...

Page 13: ...is available that allows the controller to be programmed without power OEM settings to be default settings fast copying of EPMs when multiple controllers require identical settings It can also store...

Page 14: ...rotation HIGH CCW rotation 5 Quick stop Controlled deceleration to standstill active LOW Set decel rate in C13 or c03 6 CW rotation 7 CCW rotation CW rotation LOW and CCW rotation LOW Quick stop Open...

Page 15: ...y to personnel C1 Acceleration time 1 5 0 0 0 s 999 C12 frequency change 0 Hz C11 C13 frequency change C11 0 Hz For S ramp accel decel adjust c82 Deceleration time 1 5 0 0 0 s 999 C1 Operating Mode 2...

Page 16: ...ll read 1 Disabled Configuration analog input 0 0 0 10 V 1 0 5 V 2 0 20 mA 3 4 20 mA 4 4 20 mA monitored Will trigger fault if signal falls below 2 mA Voltage DC injection brake DCB 4 0 0 0 50 0 See C...

Page 17: ...if C01 1 Start condition with mains on 1 0 Start after LOW HIGH change at terminal 28 See also c70 1 Auto start if terminal 28 HIGH WARNING Automatic starting restarting may cause damage to equipment...

Page 18: ...p c82 0 0 Adjusts S ramp curve for smoother ramp Minimum feedback 0 0 0 0 999 Select feedback signal at C34 If feedback is reverse acting set c86 c87 7 Maximum feedback 100 0 0 999 PI setpoint accel d...

Page 19: ...valid for controller Use EPM providing valid data Load Lenze setting Data error OEM data not valid EPM error EPM missing or defective Power down and replace EPM Digital inputs not uniquely assigned E...

Page 20: ...ontroller load Improve cooling Overvoltage on DC bus Mains voltage too high Check mains voltage Excessively short deceleration time or motor in generator mode Increase deceleration time or use dynamic...