EDBPM−H310   DE/EN/FR   7.1

2.2.2

Interface description 

1

2

3

4

5

6

7

8

h310_010

Fig. 2−1

ASP8 Minidin socket, 8−pin

Pin

Signal

1

Rx RS232 IN

2

Tx RS232 OUT

3

n.c.

4

RTS RS232 OUT

5

CTS RS232 IN

6

n.c.

7

Signal GND

8

+5 VCC (reserved)

n.c.

not connected

Summary of Contents for EPM-H310

Page 1: ...Betriebsanleitung EDBPM H310 K Ä Kä HMI EPM H310 Bedieneinheit Operating unit Unité de commande Operating Instructions Instructions de mise en service shift F1 Esc F2 F3 F4 F5 Help Info ...

Page 2: ...achten Sie die enthaltenen Sicherheitshinweise Please read these instructions before you start working Follow the enclosed safety instructions Veuillez lire attentivement cette documentation avant toute action Les consignes de sécurité doivent impérativement être respectées ...

Page 3: ...shift F1 Esc F2 F3 F4 F5 Help Info LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 1 2 3 0 h310_014 ...

Page 4: ...ende zur Übersicht Pos Beschreibung Funktion Klemmenleiste 4 polig DC Spannungsversorgung 24 V Trimmer LCD ADJ Display Kontrast einstellen Minidin Buchse 8 polig Serieller Port ASP für PC oder SPS Klemmenleiste 5 polig Systembus CAN ...

Page 5: ... 5 EDBPM H310 DE EN FR 7 1 Diese Dokumentation ist gültig für die Bedieneinheit EPM H310 ab der Typenschildbezeichnung Typ EPM H310 1A 10 Produktreihe EPM Bedieneinheit Hardwarestand Softwarestand ...

Page 6: ...nterneh mens 13231305 5 0 02 2008 TD23 Fimierung geändert in Lenze Digitec Controls GmbH 00473988 4 0 11 2003 TD23 Überarbeitung Fehlerbehebung 00457280 3 0 08 2002 TD23 Umfirmierung 00418421 2 0 08 2001 TD23 Komplette Überarbeitung zur Serie 00414158 1 0 03 2000 TD23 Erstauflage zum Feldtest 0Abb 0Tab 0 Tipp Dokumentationen und Software Updates zu weiteren Lenze Produkten finden Sie im Internet i...

Page 7: ...stallation 16 3 1 Bedieneinheit befestigen 16 4 ElektrischeInstallation 18 4 1 Versorgungsspannung anschließen 18 4 2 Systembus CAN verdrahten 19 5 Inbetriebnahme 21 5 1 Erstes Einschalten 21 5 3 Projekt in die Bedieneinheit übertragen 22 5 3 1 Bedieneinheit und PC verbinden 22 5 3 2 Projekt Download 23 5 3 3 Verbindung zum PC entfernen 24 5 4 Statusmeldungen der Bedieneinheit 25 5 5 Kontrast eins...

Page 8: ...Inhalt i 8 EDBPM H310 DE EN FR 7 1 8 Wartung 30 9 Anhang 31 9 1 Chemikalienbeständigkeit 31 9 2 Stichwortverzeichnis 33 ...

Page 9: ...die für sie relevanten Angaben und Hinweise beachten ƒ Die Betriebsanleitung muss stets komplett und in einwandfrei lesbarem Zustand sein 1 2 Verwendete Begriffe Begriff Im folgenden Text verwendet für Antriebsregler Lenze Frequenzumrichter 8200 vector und 9300 vector Lenze Servo Umrichter 9300 und 9400 HMI Human Machine Interface 1 3 Lieferumfang Lieferumfang Wichtig l 1 Bedieneinheit EPM H310 l ...

Page 10: ...s auf eine unmittelbar drohende Gefahr die den Tod oder schwere Verletzungen zur Folge haben kann wenn nicht die entsprechenden Maßnahmen getroffen werden Gefahr Gefahr von Personenschäden durch eine allgemeine Gefahrenquelle Hinweis auf eine unmittelbar drohende Gefahr die den Tod oder schwere Verletzungen zur Folge haben kann wenn nicht die entsprechenden Maßnahmen getroffen werden Stop Gefahr v...

Page 11: ...d Geräteschutz Schutzart IP65 frontseitig EMV Angewandte Normen zu Grenzwerten EN 61000 6 4 2007 Störaussendung Nutzungsbeschränkung Die Einhal tung der Schutzanforderungen in Wohngebieten ist nicht gewährleistet EN 61000 6 2 2005 Störfestigkeit Nutzungsbeschränkung Die Einhal tung der Schutzanforderungen in Wohngebieten ist nicht gewährleistet Einsatzbedingungen Umgebungsbedingungen Klimatisch La...

Page 12: ...meter Hintergrundbeleuchtung LED Elektrischer An schluss DC Spannungsversorgung 18 32 VDC Leistungsaufnahme 5 W bei 24 VDC Absicherung Feinsicherung Æ5 20 mm 315 mA F Netzwerk Systembus CAN Protokoll Systembus CAN Netzwerk Topologie Linie beidseitig abgeschlossen mit 120 W Systembus Teilnehmer Master oder Slave max Anzahl Teilnehmer 63 Baudrate kBit s 20 50 125 250 500 1000 max Buslänge m 2500 100...

Page 13: ...asten Anzahl 5 Funktion Bitumkehr Funktion vorhanden Direktbefehl mit Wert Struktur Echtzeitbit setzen Interner Befehl Keine Sequenz Taste deaktivieren Gleichungen Anzahl 32 Globale Eingabetasten E Tasten mit fester Funktions belegung Funktion vorhanden Globale Konfiguration Funktionstasten F Tasten Funktion vorhanden Informationsmeldungen insgesamt gleichzeitig aktiv 128 128 Interne Register Anza...

Page 14: ...ung 2 14 EDBPM H310 DE EN FR 7 1 2 2 2 Schnittstellenbeschreibung 1 2 3 4 5 6 7 8 h310_010 Abb 2 1 ASP8 Minidin 8pol Buchse Pin Signal 1 Rx RS232 IN 2 Tx RS232 OUT 3 n c 4 RTS RS232 OUT 5 CTS RS232 IN 6 n c 7 Signal GND 8 5 VCC reserved n c Nicht angeschlossen ...

Page 15: ...M H310 DE EN FR 7 1 2 3 Abmessungen d a b c shift F1 Esc F2 F3 F4 F5 e Help Info h310_001 Abb 2 2 Abmessungen a mm b mm c mm d mm e mm 166 0 86 0 27 0 4 0 41 0 2 4 Einbauausschnitt b a h312_004 Abb 2 3 Einbauausschnitt a mm b mm 77 0 157 0 ...

Page 16: ... Einbauausschnitt entnehmen Sie den technischen Daten 15 So befestigen Sie die Bedieneinheit 0 1 h310_006 1 Bedieneinheit mit Dichtung in den Einbauausschnitt schieben 0 VDC N C LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA ASP8 N C CAN Shield CAN V 1 2 3 4 5 2 1 3 4 2 2 h310_011 2 Befestigungsschellen in die Öffnungsschlitze der Bedieneinheit schieben ...

Page 17: ...en 3 17 EDBPM H310 DE EN FR 7 1 0 VDC N C LC D ADJ 24 VDC INPUT 18 32 V 5W FU SE 315 mA ASP8 N C CAN Shield CAN V 1 2 3 4 5 2 1 3 4 3 2 3 h310_009 3 Schrauben in die Befestigungsschellen drehen 4 Schrauben gegen die Einbautafel drehen und festziehen ...

Page 18: ...ieneinheit nur im spannungslosen Zustand verdrahten 4 1 Versorgungsspannung anschließen LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 PE N L1 18 32VDC h310_003 Abb 4 1 Anschluss der Versorgungsspannung Klemmenbelegung Klemme Bezeichnung Erläuterung 1 DC 24 V Versorgungsspannung DC 18 V 32 V 2 DC 0 V GND Versorgungsspannung Bezugspotential 3 n c N...

Page 19: ...N finden Sie im Kommunikationshandbuch CAN Prinzipieller Aufbau Shield CAN V CAN N C CG LO HI CG LO CG LO HI CG LO HI HI 120 120 An A2 H310 A1 h310_004 Abb 4 2 Verdrahtung des Systembus CAN A1 Busteilnehmer 1 A2 Busteilnehmer 2 An Busteilnehmer n Anschluss LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 CAN GND CAN LO CAN HI h310_015 Abb 4 3 Anschl...

Page 20: ...tung 3 Shield Schirm des Systembus Kabels auflegen 4 CAN HI Systembus HIGH Datenleitung 5 n c Nicht angeschlossen Für einen störungsfreien Betrieb verwenden Sie Leitungen mit der angegebe nen Spezifikation Spezifikation der Leitung Gesamtlänge 300 m 1000 m Leitungstyp LIYCY 2 x 2 x 0 5 mm2 paarweise verdrillte und abge schirmte Adern CYPIMF 2 x 2 x 0 5 mm2 paarweise verdrillte und abge schirmte Ad...

Page 21: ...halten Für die Inbetriebnahme ist eine vollständige Verdrahtung des Systembus not wendig ÜberprüfenSie vor dem Einschalten der Versorgungsspannung ƒ die gesamte Verdrahtung auf Vollständigkeit und Kurzschluss ƒ ob das Bussystem beim physikalisch ersten und letzten Busteilnehmer abgeschlossen ist ...

Page 22: ...en PC und Bedieneinheit nur bei ausgeschalteten Geräten herstellen l HMI Designer LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 0 1 2 h310_005 Abb 5 1 Bedieneinheit und PC verbinden 1 Programmieradapter EPZ H111 auf die ASP8 Schnittstelle stecken 2 Downloadkabel EPZ H110 mit Programmieradapter EPZ H111 verbinden 3 Downloadkabel EPZ H110 auf COM1 ...

Page 23: ... im Projektierungstool HMI Designer unter Datei Öffnen Samples 0 shift F1 Esc F2 F3 F4 F5 Help Info h310_007 So übertragen Sie ein Projekt in die Bedieneinheit 1 PC einschalten und Projektierungstool HMI Designer starten 2 Bedieneinheit einschalten A Enter Taste an der Bedieneinheit gedrückt halten B Versorgungsspannung für Bedieneinheit einschalten C Enter Taste loslassen wenn im Display H310 Ser...

Page 24: ...3 Verbindung zum PC entfernen So entfernen Sie die Verbindung zum PC 1 PC ausschalten 2 Versorgungsspannung für Bedieneinheit abschalten 3 Programmieradapter EPZ H111 an der Bedieneinheit und Downloadkabel EPZ H110 am PC abziehen 4 Versorgungsspannung für Bedieneinheit einschalten Die Bedieneinheit ist betriebsbereit ...

Page 25: ...zuletzt aufgetretene Störung Error Sie möchten Drücken Sie die Tasten Beispiel A den Status der Bedieneinheit abfragen shift 2x Driver Can Lenze M Ver 1 05 B die nächste Statusseite anwählen Help á oder Info â Addr NO ADDRESS Error RESET C die Statusanzeige schließen F1 Esc 5 4 Kontrast einstellen LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 0 h...

Page 26: ... Zeile stellen Parameter Ebene Cursor auf die nächste Ziffer stellen shift F4 F4 Funktion von F4 ausführen Taste programmierbar F4 Parameter auswäh len Parameter zum Eingeben des Wertes anwählen shift F5 F5 Funktion von F5 ausführen Taste programmierbar F5 Eingabe bestätigen Übernehmen des eingegebenen Wertes shift Help á Help Hilfe Text aufrufen Taste programmierbar Help á Pfeil auf Menü Ebene Zu...

Page 27: ... oder Info â Feld 1 ON Feld 2 9869 2 Bestätigen Sie die Eingabe Der Cursor wechselt in die Menü Ebene F5 F eine einzelne Ziffer der Zahl verändern 1 Wählen Sie die gewünschte Ziffer F2 ß oder F3 à Feld 1 ON Feld 2 9 76 3 2 Ändern Sie die Ziffer Help á oder Info â 3 Bestätigen Sie die Eingabe Der Cursor wechselt in die Menü Ebene F5 G ein Komma setzen 1 Wählen Sie die Position an der Sie das Komma ...

Page 28: ...en Beispiel A eine Informationsmeldung aufrufen shift Info â Druck übersteigt die Sicherheitsgrenze B die vorherige oder nächste Informationsmel dung anwählen Help á oder Info â Wasserstand unterhalb d Arbeitsschwelle C die Informationsmeldung schließen F1 Esc 6 4 Hilfemeldung aufrufen ƒ Hilfemeldungen können Seiten oder Informationsmeldungen zugeordnet sein enthalten nützliche Hinweise die die Be...

Page 29: ...en Sitz prüfen l Leitung auf Beschädigung kontrollie ren COM BROK Kommunika tion unterbro chen Serielles Datenkabel zwischen Bedieneinheit und PC ist defekt oder nicht richtig angeschlossen l Sub D Stecker auf richtigen An schluss und festen Sitz prüfen l Serielles Datenkabel austauschen ASIC ko1 Kommunika tion mit Sys tembus CAN unterbrochen l Fehlerhafte Verdrahtung z B Verpolung des System bus ...

Page 30: ...rei wenn die vorgeschriebenen Einsatzbedin gungen eingehalten werden 11 ƒ Reinigen Sie die Bedieneinheit mit denaturiertem Äthylalkohol ƒ Wenn Sie ein anderes Reinigungsmittel verwenden müssen um Verunreinigungen zu beseitigen beachten Sie die Angaben in der Tabelle im Kap 9 1 31 ...

Page 31: ...PM H5xx und EPM H6xx bietet Lenze Schutzfolien an mit einer verbesserten Beständigkeit gegen die genannten Chemikalien Substanz Bedieneinheit EPM H3xx EPM H4xx EPM H5xx EPM H6xx mit Schutz folie Aceton L L J Ameisensäure 50 L L Ammoniak 2 L L Äthylenglykol L L L Ätznatron 2 L L Beizlösung konzentriert L Benzin J L L J Benzol J J L J Benzylalkohol L L Chlorwasserstoffsäure 10 L L Dieselöl J J J J E...

Page 32: ...50 L L L L Toluol J J L J Trichlorethylen L J Unterchlorigsaures Na tron 20 L L Wasserstoffsuperoxyd 25 L L EPM H3xx EPM H310 EPM H312 EPM H315 EPM H4xx EPM H410 EPM H5xx EPM H502 EPM H505 EPM H507 EPM H510 EPM H515 EPM H520 EPM H521 EPM H525 EPM H6xx EPM H605 EPM H606 J Oberfläche ist beständig keine sichtbare Beschädigung L Oberfläche ist nicht beständig wird beschädigt nicht getestet ...

Page 33: ...eben 27 DC Spannungsversorgung 12 Definition der verwendeten Hinweise 10 Display 12 Kontrast einstellen 25 E Eigenschaften 13 Einbauausschnitt 15 Einsatzbedingungen 11 Feuchtebeanspruchung 11 Montagebedingungen Gewicht 11 Umgebungsbedingungen klimatisch 11 Einschalten erstes 21 Elektrische Daten 12 Elektrische Installation 18 Versorgungsspannung anschließen 18 Erstes Einschalten 21 F Fehlersuche 2...

Page 34: ...neinheit übertragen 22 Projekt Download 23 S Sicherheitshinweise Definition 10 Gestaltung 10 Speicher 12 Statusmeldungen 25 Störungsbeseitigung 29 Störungsmeldungen 29 Systembus CAN Baudrate 12 Verdrahtung 19 T Tastenfunktionen 26 Technische Daten 11 DC Spannungsversorgung 12 Display 12 Einbauausschnitt 15 Elektrische Daten 12 elektrischer Anschluß 12 Leistungsaufnahme 12 Schnittstellenbeschreibun...

Page 35: ...Anhang Stichwortverzeichnis 9 35 EDBPM H310 DE EN FR 7 1 ...

Page 36: ... 7 1 Key for the overview Pos Description Function Terminal strip 4 pole DC voltage supply 24 V Trimmer LCD ADJ Setting display contrast Minidin 8 pole socket ASP serial port for PC or PLC Terminal strip 5 pole System bus CAN ...

Page 37: ...37 EDBPM H310 DE EN FR 7 1 This documentation applies to EPM H310 operating units as of the following nameplate data Type EPM H310 1A 10 Product range EPM operating unit Hardware version Software version ...

Page 38: ...e company 13231305 5 0 02 2008 TD23 Change of company name to Lenze Digitec Controls GmbH 00473988 4 0 11 2003 TD23 Revision error correction 00457280 3 0 08 2002 TD23 Change of company name 00418421 2 0 08 2001 TD23 Complete revision of series 00414158 1 0 03 2000 TD23 First edition for field test 0Fig 0Tab 0 Tip Documentation and software updates for further Lenze products can be found on the In...

Page 39: ...installation 49 3 1 Attaching operating unit 49 4 Electrical installation 51 4 1 Supply voltage connection 51 4 2 Wiring of the system bus CAN 52 5 Commissioning 54 5 1 Initial switch on 54 5 3 Project transfer to the operating unit 55 5 3 1 Connecting operating unit and PC 55 5 3 2 Project download 56 5 3 3 Disconnectingfrom the PC 57 5 4 Status messages of the operating unit 58 5 5 Contrast sett...

Page 40: ...Contents i 40 EDBPM H310 DE EN FR 7 1 8 Maintenance 63 9 Appendix 64 9 1 Chemical resistance 64 9 2 Index 66 ...

Page 41: ...e and observe all relevant information and notes ƒ These Operating Instructions must always be kept as a complete document and in a readable state 1 2 Terminology used Term Used in this text for Controller Lenze 8200 vector and 9300 vector frequency inverter Lenze 9300 and 9400 servo inverter HMI Human Machine Interface 1 3 Scope of supply Scope of supply Important l 1 EPM H310 operating unit l 1 ...

Page 42: ...rough dangerous electrical voltage Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken Danger Danger of personal injury through a general source of danger Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken Stop Danger of property damage Reference ...

Page 43: ...otection of persons and equipment Enclosure IP65 front EMC Applied standards for limit values EN 61000 6 4 2007 Noise emission Restriction of use Protection requirements are not ensured in residential areas EN 61000 6 2 2005 Noise immunity Restriction of use Protection requirements are not ensured in residential areas Operating conditions Ambient conditions Climate Storage 20 60 C Transport 20 60 ...

Page 44: ...ming potentiometer Background illumination LED Electrical connection DC voltage supply 18 32 VDC Power consumption 5 W at 24 VDC Fusing Micro fuse Æ5 20 mm 315 mA F Network System bus CAN Protocol System bus CAN Network topology Line terminated at both ends with 120 W System bus station Master or slave Max number of stations 63 Baud rate kbit s 20 50 125 250 500 1000 Max bus length m 2500 1000 500...

Page 45: ...available Freely definable function keys F keys Number 5 Function Bit inversion Function available Direct command with value structure Set real time bit Internal command None Sequence Deactivate key Equations Number 32 Global enter keys E keys with fixed function assignment Function available Global configuration function keys F keys Function available Information messages Total active at the same...

Page 46: ...cal data Electrical data Features of the operating unit 2 46 EDBPM H310 DE EN FR 7 1 Values Description Variables Numeric variables DEC HEX BIN BCD Number per page 8 1 guide value limited by the project size ...

Page 47: ...ion 2 47 EDBPM H310 DE EN FR 7 1 2 2 2 Interface description 1 2 3 4 5 6 7 8 h310_010 Fig 2 1 ASP8 Minidin socket 8 pin Pin Signal 1 Rx RS232 IN 2 Tx RS232 OUT 3 n c 4 RTS RS232 OUT 5 CTS RS232 IN 6 n c 7 Signal GND 8 5 VCC reserved n c not connected ...

Page 48: ...PM H310 DE EN FR 7 1 2 3 Dimensions d a b c shift F1 Esc F2 F3 F4 F5 e Help Info h310_001 Fig 2 2 Dimensions a mm b mm c mm d mm e mm 166 0 86 0 27 0 4 0 41 0 2 4 Mounting cutout b a h312_004 Fig 2 3 Mounting cutout a mm b mm 77 0 157 0 ...

Page 49: ...ions for the mounting cutout can be found in the Technical data 48 How to mount the operating unit 0 1 h310_006 1 Insert operating unit with seal into the mounting cut out 0 VDC N C LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA ASP8 N C CAN Shield CAN V 1 2 3 4 5 2 1 3 4 2 2 h310_011 2 Insert mounting clamps into the slots at the operating unit ...

Page 50: ...ating unit 3 50 EDBPM H310 DE EN FR 7 1 0 VDC N C LC D ADJ 24 VDC INPUT 18 32 V 5W FU SE 315 mA ASP8 N C CAN Shield CAN V 1 2 3 4 5 2 1 3 4 3 2 3 h310_009 3 Insert screws into mounting clamps 4 Tighten the screws against the mounting board ...

Page 51: ...ting unit only when no voltage is applied 4 1 Supply voltage connection LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 PE N L1 18 32VDC h310_003 Fig 4 1 Supply voltage connection Terminal assignment Terminal Identification Explanation 1 24 VDC Supply voltage DC 18 V 32 V 2 0 VDC GND supply voltage reference potential 3 n c Not connected 4 PE poten...

Page 52: ...o the system bus CAN please refer to the CAN Communication Manual Principle structure Shield CAN V CAN N C CG LO HI CG LO CG LO HI CG LO HI HI 120 120 An A2 H310 A1 h310_004 Fig 4 2 Wiring of system bus CAN A1 Node 1 A2 Node 2 An Node n Connection LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 CAN GND CAN LO CAN HI h310_015 Fig 4 3 System bus CAN ...

Page 53: ...tem bus LOW data line 3 Shield Connect the shield of the system bus cable 4 CAN HI System bus HIGH data line 5 n c Not connected For trouble free operation use cables with the listed specifications Cable specifications Overall length 300 m 1000 m Cable type LIYCY 2 x 2 x 0 5 mm2 twisted in pairs and shielded cores CYPIMF 2 x 2 x 0 5 mm2 twisted in pairs and shielded cores Cable resistance 80 W km ...

Page 54: ...missioning 5 1 Initial switch on Commissioning requires a complete wiring of the system bus Before switching on the supply voltage check ƒ the complete wiring for completeness and short circuit ƒ whether the bus system is terminated at the first and last physical node ...

Page 55: ...nect PC and operating unit when the units are switched off l HMI Designer LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 0 1 2 h310_005 Fig 5 1 Connecting operating unit and PC 1 Plug the programming adapter EPZ H111 onto the ASP8 interface 2 Connect download cable EPZ H110 to programming adapter EPZ H111 3 Plug download cable EPZ H110 onto COM1 o...

Page 56: ...MI Designer planning tool under File Open Samples 0 shift F1 Esc F2 F3 F4 F5 Help Info h310_007 How to download a project into the operating unit 1 Switch on your PC and start the HMI Designer planning tool 2 Switch on the operating unit A Keep the enter key of the operating unit pressed B Switch on the supply voltage for the operating unit C Let go of the enter key when H310 Service Page appears ...

Page 57: ...g from the PC How to disconnect from the PC 1 Switch off the PC 2 Switch off the supply voltage for the operating unit 3 Unplug the EPZ H111 programming adapter from the operating unit and the EPZ H110 download cable from the PC 4 Switch on the supply voltage for the operating unit The operating unit is now ready for operation ...

Page 58: ...he operating unit ƒ The last error If you want to Press keys Example A query the status of the operating unit shift 2x Driver Can Lenze M Ver 1 05 B select the next status page Help á or Info â Addr NO ADDRESS Error RESET C close the status message F1 Esc 5 4 Contrast setting LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 0 h310_008 How to set the...

Page 59: ...ce cursor in next line Parameter level Place cursor on next digit shift F4 F4 Execute function of F4 programmable key F4 Select parameter Select parameter to enter a value shift F5 F5 Execute function of F5 programmable key F5 Confirm input Accept the entered value shift Help á Help Call up help text programmable key Help á Up arrow Menu level Go to previous page Parameter level Input of digits 0 ...

Page 60: ... Info â Field 1 ON Field 2 9869 2 Confirm the input The cursor changes to the menu level F5 F change a digit of a number 1 Select the desired digit F2 ß or F3 à Field 1 ON Field 2 9 76 3 2 Change the digit Help á or Info â 3 Confirm the input The cursor changes to the menu level F5 G set a point 1 Select the position where the point is to be inserted F2 ß or F3 à Field 1 ON Field 2 9 76 2 Change t...

Page 61: ...available or not If you want to Press keys Example A call up an information message shift Info â Pressureexceeds safetylimit B select the previous or next information message Help á or Info â Waterlevelbelow workingtreshold C close the information message F1 Esc 6 4 Calling up help messages ƒ Help messages can be assigned to page or information messages contain useful notes to make handling easier...

Page 62: ...nnections are firmly seated l Check cable for damages COM BROK Communication interrupted Serial data cable between operating unit and PC is defective or not correctly connected l Check Sub D connector for correct connection and firm seating l Replace serial data cable ASIC ko1 Communication with system bus CAN interrupted l Faulty wiring e g polarity of the system bus l Faulty parameterisation of ...

Page 63: ...ing unit is maintenance free if all operating conditions described in these Instructions are observed 43 ƒ Clean the operating unit with denatured ethyl alcohol ƒ If you use any other cleaning agents please observe the information given in the table in chapter 9 1 64 ...

Page 64: ...rating units Lenze offers protective foils with an improved resistance against the listed chemicals Substance Operating unit EPM H3xx EPM H4xx EPM H5xx EPM H6xx With protective foil Acetic acid 5 50 L L L J Acetone L L J Ammonia 2 L L Benzene J L L J Benzole J J L J Benzyl alcohol L L Diesel oil J J J J Ethanol L L L J Ethylene glycol L L L Formic acid 50 L L High pressure and temperature 100 C L ...

Page 65: ...Concentrated L Pure acetic acid L L Sodium hydroxide 2 L L Sodium hydroxide 50 L L L Sulphuric acid 50 L L L L Toluol J J L J Trichloroethylene L J EPM H3xx EPM H310 EPM H312 EPM H315 EPM H4xx EPM H410 EPM H5xx EPM H502 EPM H505 EPM H507 EPM H510 EPM H515 EPM H520 EPM H521 EPM H525 EPM H6xx EPM H605 EPM H606 J Surface resists no visible damage L Surface does not resist visible damage Not tested ...

Page 66: ...ut 60 DC voltage supply 44 Definition of notes used 42 Definitions 41 Display 44 contrast setting 58 E Electrical data 44 Electrical installation 51 Connecting the supply voltage 51 F Fault messages 62 G General data 43 H Help messages 61 Human Machine Interface 41 Humidity 43 I Information messages 61 Initial switch on 54 Installation system bus CAN 52 Installation electrical 51 Installation elec...

Page 67: ...s messages 58 Operation 59 P Parameters 45 PC Connecting with the operating unit 55 Disconnecting from the operating unit 57 Power consumption 44 Project Download 56 Project transfer to the operating unit 55 S Safety instructions definition 42 layout 42 Status messages 58 Switch on initial 54 System bus CAN Baud rate 44 Wiring 52 T Technical data 43 DC voltage supply 44 Display 44 Electrical conne...

Page 68: ...0 DE EN FR 7 1 Légende Pos Description Fonction Bornier à 4 bornes Alimentation 24 V CC Trimmer LCD ADJ Réglage du contraste Prise Minidin à 8 broches Port série ASP pour PC ou API Bornier à 5 bornes Bus Système CAN ...

Page 69: ... H310 DE EN FR 7 1 Validité Unité de commande EPM H310 à partir de la version ci dessous voir plaque signalétique Type EPM H310 1A 10 Série d appareils EPM Unité de commande Version matérielle Version logicielle ...

Page 70: ...rise 13231305 5 0 02 2008 TD23 Nouvelle raison sociale Lenze Digitec Controls GmbH 00473988 4 0 11 2003 TD23 Révision rectification des erreurs 00457280 3 0 08 2002 TD23 Changement de raison sociale 00418421 2 0 08 2001 TD23 Texte entièrement revu pour la série 00414158 1 0 03 2000 TD23 Première édition pour essais sur le terrain 0Fig 0Tab 0 Conseil Les mises à jour de logiciels et les documentati...

Page 71: ...ontage de l unité de commande 81 4 Installationélectrique 83 4 1 Raccordement de la tension d alimentation 83 4 2 Câblage du Bus Système CAN 84 5 Mise en service 86 5 1 Première mise en service 86 5 3 Téléchargementd un projet sur l unité de commande 87 5 3 1 Etablissement de la liaison entre l unité de commande et le PC 87 5 3 2 Téléchargement du projet 88 5 3 3 Déconnexiondu PC 89 5 4 Messages d...

Page 72: ...Sommaire i 72 EDBPM H310 DE EN FR 7 1 8 Maintenance 96 9 Annexe 97 9 1 Résistance aux produits chimiques 97 9 2 Index 99 ...

Page 73: ...indications et consignes correspondantes ƒ Les instructions de mise en service doivent être complètes et lisibles en toute circonstance 1 2 Terminologie Terme Utilisé dans le présent document pour désigner Variateur de vitesse les convertisseurs de fréquence 8200 vector et 9300 vector et les servovariateurs 9300 et 9400 de Lenze HMI une interface homme machine Human Machine Interface 1 3 Equipemen...

Page 74: ...nséquences des blessures mortelles ou très graves en cas de non respect des consignes de sécurité correspondantes Danger Situation dangereuse pour les personnes en raison d un danger d ordre général Indication d un danger imminent qui peut avoir pour conséquences des blessures mortelles ou très graves en cas de non respect des consignes de sécurité correspondantes Stop Risques de dégâts matériels ...

Page 75: ...il Indice de protection IP65 à l avant CEM Normes appliquées pour les valeurs limites EN 61000 6 4 2007 Perturbations radioélectriques Restriction d utilisation en environnement résidentiel le respect des exigences de protection n est pas garanti EN 61000 6 2 2005 Protection contre les parasites Restriction d utilisation en environnement résidentiel le respect des exigences de protection n est pas...

Page 76: ...e trimmer Rétro éclairage LED Raccordement électrique Alimentation CC 18 à 32 VCC Puissance absorbée 5 W pour 24 VCC Protection par fusible Fusible pour faible intensité Æ5 20 mm 315 mA F Réseau Bus Système CAN Protocole Bus Système CAN Topologie du réseau Ligne fermée des deux extrémités avec 120 W Participant au Bus Système Maître ou esclave Nombre maxi de participants 63 Vitesse de transmission...

Page 77: ...aleur nombre 1024 1 Etiquettes fonction oui Touches de fonction configurables touches F nombre 5 Fonction Inversion bit fonction oui Instruction directe avec structure valeur Activer bit temps réel Instruction interne Sans fonction Séquence Désactiver la touche Equations nombre 32 Touches de saisie globales touches E avec fonctions fixes fonction oui Configuration globale des touches de fonction t...

Page 78: ...électriques Caractéristiques de l unité de commande 2 78 EDBPM H310 DE EN FR 7 1 Données Description Temporisateur nombre 20 Variables Variables numériques DEC HEX BIN BCD nombre par page 8 1 Valeur approximative limitée par la grandeur process ...

Page 79: ...on de la prise 2 79 EDBPM H310 DE EN FR 7 1 2 2 2 Affectation de la prise 1 2 3 4 5 6 7 8 h310_010 Fig 2 1 Prise ASP8 Minidin à 8 broches Pin Signal 1 Rx RS232 IN 2 Tx RS232 OUT 3 N C 4 RTS RS232 OUT 5 CTS RS232 IN 6 N C 7 Signal GND 8 5 VCC réservé N C Non connecté ...

Page 80: ...BPM H310 DE EN FR 7 1 2 3 Encombrements d a b c shift F1 Esc F2 F3 F4 F5 e Help Info h310_001 Fig 2 2 Encombrements a mm b mm c mm d mm e mm 166 0 86 0 27 0 4 0 41 0 2 4 Encoche de montage b a h312_004 Fig 2 3 Encoche de montage a mm b mm 77 0 157 0 ...

Page 81: ... encoche de montage se reporter aux Spécifications techniques 80 Pour fixer l unité de commande 0 1 h310_006 1 Glisser l unité de commande avec le joint dans l encoche de montage 0 VDC N C LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA ASP8 N C CAN Shield CAN V 1 2 3 4 5 2 1 3 4 2 2 h310_011 2 Placer les colliers de fixation dans les ouvertures prévues à cet effet ...

Page 82: ...ité de commande 3 82 EDBPM H310 DE EN FR 7 1 0 VDC N C LC D ADJ 24 VDC INPUT 18 32 V 5W FU SE 315 mA ASP8 N C CAN Shield CAN V 1 2 3 4 5 2 1 3 4 3 2 3 h310_009 3 Introduire les vis dans les colliers de fixation 4 Visser la plaque de montage ...

Page 83: ...lage de l unité de commande qu en l absence de tension 4 1 Raccordement de la tension d alimentation LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 PE N L1 18 32VDC h310_003 Fig 4 1 Raccordement de la tension d alimentation Affectation des bornes Borne Désignation Explication 1 24 V CC Tension d alimentation 18 V 32 V CC 2 0 V CC GND tension d ali...

Page 84: ...porter au manuel de communication CAN Principe de câblage Shield CAN V CAN N C CG LO HI CG LO CG LO HI CG LO HI HI 120 120 An A2 H310 A1 h310_004 Fig 4 2 Câblage du Bus Système CAN A1 Participant au bus 1 A2 Participant au bus 2 An Participant au bus n Raccordement LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 CAN GND CAN LO CAN HI h310_015 Fig 4...

Page 85: ...référence 2 CAN LO Bus Système LOW ligne de données 3 Shield Blindage du câble bus 4 CAN HI Bus Système HIGH ligne de données 5 N C Non raccordé Pour assurer le bon fonctionnement utiliser des câbles conformes aux spécifications suivantes Spécifications du câble Longueur totale 300 m 1000 m Type de câble LIYCY 2 x 2 x 0 5 mm2 paire blindée CYPIMF 2 x 2 x 0 5 mm2 paire blindée Résistance de câble 8...

Page 86: ... mise en service Pour la mise en service il est impératif que le Bus Système soit correctement raccordé Avant la mise sous tension vérifier ƒ le câblage dans son intégralité pour éviter un court circuit ƒ si des résistances d extrémité de bus sont raccordées au premier et au dernier participant au bus ...

Page 87: ... Stop Ne relier le PC à l unité de commande qu en l absence de tension l HMI Designer LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 0 1 2 h310_005 Fig 5 1 Etablissement de la liaison entre l unité de commande au PC 1 Enficher l adaptateur de paramétrage EPZ H111 dans la prise ASP8 2 Relier le câble de téléchargement EPZ H110 avec l adaptateur EPZ...

Page 88: ...e commande voir l outil de conception HMI Designer Fichier Ouvrir Samples modèles 0 shift F1 Esc F2 F3 F4 F5 Help Info h310_007 Pour charger un projet sur l unité de commande 1 Mettre le PC sous tension et démarrer l outil de conception HMI Designer 2 Mise sous tension de l unité de commande A Appuyer sans relâcher sur la touche Enter de l unité de commande B Mettre l unité de commande sous tensio...

Page 89: ... 5 2 3 Déconnexion du PC Pour couper la liaison avec le PC 1 Mettre le PC hors tension 2 Mettre l unité de commande hors tension 3 Retirer l adaptateur EPZ H111 de l unité de commande et le câble de téléchargement EPZ H110 du PC 4 Mettre l unité de commande sous tension L unité de commande est prête à fonctionner ...

Page 90: ...ƒ dernier défaut en date Error Pour appuyer sur les touches Exemple A connaître l état de l unité de commande shift 2x Driver Can Lenze M Ver 1 05 B sélectionner la page d état suivante Help á ou Info â Addr NO ADDRESS Error RESET C fermer l affichage d état F1 Esc 5 4 Réglage du contraste LCD ADJ 24 VDC INPUT 18 32 V 5W FUSE 315 mA 0 VDC N C ASP8 N C CAN Shield CAN V 1 1 2 3 4 5 2 3 4 0 h310_008 ...

Page 91: ...dans la ligne suivante Niveau paramètres placer le curseur sur le chiffre suivant shift F4 F4 Exécuter la fonction de F4 touche configurable F4 Sélectionner le code Sélectionner le code pour entrer la valeur shift F5 F5 Exécuter la fonction de F5 touche configurable F5 Validation Valider la valeur entrée shift Help á Help Afficher l aide touche configurable Help á Touche de direction HAUT Niveau m...

Page 92: ...876 E compter ou décompter les chiffres entiers 1 Laisser le curseur sur le chiffre droit Help á ou Info â Feld 1 ON Feld 2 9869 2 Valider Le curseur passe au niveau menu F5 F modifier un chiffre individuel du nombre 1 Sélectionner le chiffre souhaité F2 ß ou F3 à Feld 1 ON Feld 2 9 76 3 2 Modifier le chiffre Help á ou Info â 3 Valider Le curseur passe au niveau menu F5 G mettre une virgule 1 Séle...

Page 93: ... données 6 93 EDBPM H310 DE EN FR 7 1 Exemple appuyer sur les touches Pour H modifier une zone de texte dynamique 1 Sélectionner le texte Help á ou Info â Feld 1 FF O Feld 2 9876 2 Valider Le curseur passe au niveau menu F5 ...

Page 94: ...ponible Pour appuyer sur les touches Exemple A afficher un message d information shift Info â Pression limitede sécuritéatteinte B afficher le message précédent ou suivant Help á ou Info â Niveaud eau seuil inférieuratteint C fermer le message d information F1 Esc 6 4 Recherche d une rubrique d aide ƒ Les messages d aide peuvent être affectés aux pages ou aux messages d information contiennent des...

Page 95: ...nt bien serrés l Vérifier si le câble est endommagé COM BROK Communication interrompue Le câble de données série reliant l unité de commande et le PC est défectueux ou n est pas correctement connecté l Vérifier si le connecteur Sub D est correctement enfiché l Echanger le câble de données série ASIC ko1 Communication avec Bus Système CAN interrompue l Câblage erroné exemple polarité incorrecte du ...

Page 96: ... aucun entretien à condition de respecter les conditions d utilisation prescrites 75 ƒ Il convient de nettoyer l unité de commande à l aide d alcool éthylique dénaturé ƒ Si cette opération est insuffisante et s il faut utiliser un autre produit nettoyant se reporter au tableau chap 9 1 97 ...

Page 97: ...e commande EPM H5xx et EPM H6xx Lenze vous propose des protecteurs d écran avec une résistance améliorée aux produits chimiques mentionnés Substance Unité de commande EPM H3xx EPM H4xx EPM H5xx EPM H6xx Avec protecteur d écran Acétone L L J Acide acétique 5 50 L L L J Acide acétique glacial L L Acide chlorhydrique 10 L L Acide formique 50 L L Acide nitrique 5 10 L L L J Acide phosphorique 30 L L L...

Page 98: ... hydrogène 25 L L Tétrachloréthylène L J Toluène J J L J Trichloréthylène L J EPM H3xx EPM H310 EPM H312 EPM H315 EPM H4xx EPM H410 EPM H5xx EPM H502 EPM H505 EPM H507 EPM H510 EPM H515 EPM H520 EPM H521 EPM H525 EPM H6xx EPM H605 EPM H606 J L interface opérateur résiste à la substance chimique aucun endommagement visible L L interface opérateur ne résiste pas à la substance chimique interface opé...

Page 99: ...Définition 74 Présentation 74 Contraste réglage 90 D Définition des remarques utilisées 74 Détection des défauts 95 Messages d erreur 95 Données saisie des données 92 E Ecran 76 Réglage du contraste 90 Electricité installation Raccordement de la tension d alimentation 83 Elimination des défauts 95 Encoche de montage 80 F Fonction des touches 91 H Humidité admissible 75 I Installation Bus Système C...

Page 100: ... Rubrique d aide 94 S Spécifications techniques Affectation de la prise 79 Alimentation CC 76 Bus Système CAN 76 Caractéristiques électriques 76 Ecran 76 Encoche de montage 80 Mémoire 76 Puissance absorbée 76 Raccordement électrique 76 Spécifications techniques 75 T Terminologie 73 Type de câble CAN 85 U Unité de commande Déconnexion du PC 89 Affectation de la prise 79 Appeler un message d informa...

Page 101: ...Annexe Index 9 101 EDBPM H310 DE EN FR 7 1 ...

Page 102: ...many Service Lenze Service GmbH Breslauer Straße 3 D 32699 Extertal Germany 49 0 51 54 82 0 00 80 00 24 4 68 77 24 h helpline Ê 49 0 51 54 82 28 00 Ê 49 0 51 54 82 11 12 Lenze Lenze de Service Lenze de ü www Lenze com EDBPM H310 K DE EN FR 7 1 TD23 10 9 8 7 6 5 4 3 2 1 ...

Reviews: