6
Electrical installation
Wiring according to EMC
EDK2192IB DE / EN / FR 2.0
38
l
H1_E_INST−emv
6
Electrical installation
Wiring according to EMC
For wiring according to EMC requirements observe the following points:
)
Note!
ƒ
Separate control cables/data lines from motor cables.
ƒ
Connect the shields of control cables/data lines
at both ends
in the case of
digital signals.
ƒ
Use an equalizing conductor with a cross−section of at least 16mm
2
(reference:PE) to avoid potential differences between the bus nodes.
ƒ
Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.