Electrical installation
Connection of system bus (CAN)
EDKMF2180 DE/EN/FR/ES/IT 4.0
54
H1_E_INST−SteckerFederkraftAnschluss FKCT
Segment cable length
The segment cable length is determined by the cable cross−section used and by the number
of nodes. Repeaters divide the total cable length into segments. If no repeaters are used, the
segment cable length is identical to the total cable length.
Max. number of
nodes per
segment
Cable cross−section
(can be interpolated)
0.25 mm
2
(AWG24)
0.5 mm
2
(AWG21)
0.75 mm
2
(AWG19)
1.0 mm
2
(AWG18)
2
240 m
430 m
650 m
940 m
5
230 m
420 m
640 m
920 m
10
230 m
410 m
620 m
900 m
20
210 m
390 m
580 m
850 m
32
200 m
360 m
550 m
800 m
63
170 m
310 m
470 m
690 m
100
150 m
270 m
410 m
600 m
Tab. 2
Segment cable length
Example: Selection help
Given
Total cable length to be implemented
200 m
Number of nodes
63
Results
Max. possible baud rate
250 kbps
(derived from Tab. 1 Total cable length)
Required cable cross−section
(interpolated)
0.30 mm
2
(AWG23)
(derived from Tab. 2 Segment cable length)
Cable cross−section of standard CAN
cable
0.34 mm
2
(AWG22)
(see specification of the transmission cable
Summary of Contents for EMF2180IB
Page 3: ...ausklappbild 2180FEW001D ...
Page 33: ...Diagnose LED Statusanzeigen 8 EDKMF2180 DE EN FR ES IT 4 0 33 H1_Diagnose st_00tu0 ...
Page 63: ...Diagnostics LED status displays 8 EDKMF2180 DE EN FR ES IT 4 0 63 H1_Diagnose st_00tu0 ...
Page 93: ...Diagnostic Affichages d état par LED 8 EDKMF2180 DE EN FR ES IT 4 0 93 H1_Diagnose st_00tu0 ...