Electrical installation
Safety engineering
l
74
EDKLCFH3024−XPM DE/EN 6.0
Detailed properties of the inputs and outputs
Signal
Specification
Min.
Typ.
Max.
I1A, I1B
I2A, I2B
I4A, I4B
AIE
PLC input, IEC−61131−2, 24 V, type 1
LOW signal
[V]
−3
0
5
Input current
[mA]
15
HIGH signal
[V]
15
24
30
Input current
[mA]
2
15
Input capacitance
[nF]
3.3
AIE
Pulse duration
[ms]
300
10
4
CLA, CLB
PLC output, IEC−61131−2, 24 V DC, 50 mA
Output voltage for LOW signal
[V]
0
0.8
Output voltage for HIGH signal
[V]
17
24
29
Output current
[mA]
50
Width of test pulse
[
m
s]
750
Frequency of test pulse
[s]
1.8
Specific resistance of a passive sensor
[k
W
]
2