Electrical installation
DeviceNet connection
EDK94AYCDN DE/EN/FR/ES/IT 4.0
36
H1_E_INST−busltgslaenge
Plug connector assignment
The bus of the communication module is connected via the 5−pole plug connector with
double screw connection (X225).
E94YCDN001C
Designation
Cable colour
Description
V+
red
External voltage supply
l
U = 24 V DC
l
I
max
= 170 mA
CAN_H
white
Data line / input for bus terminating resistor (120
W
)
SHIELD
Shielding
CAN_L
blue
Data line / input for bus terminating resistor (120
W
)
V−
black
Reference potential for external voltage supply