E94AYCCA communication manual (CANopen®)
Parameter data transfer
Identifiers of the parameter data objects
62
L
EDS94AYCCA EN 5.0 - 06/2012
9.1
Identifiers of the parameter data objects
In the Lenze setting, the identifier for the parameter data objects SDO1 ... SDO10 results
from a basic identifier and the node address set in
/
Identifier (COB-ID) = basic iden node address (node ID)
In the Lenze setting, the basic identifiers of the SDOs are preset according to the
"Predefined Connection Set" of DS301, V4.02:
Parameter data object
Direction
Basic identifier
from the device
to the device
dec
hex
SDO1
(Parameter data channel 1)
z
1408
580
z
1536
600
SDO2 ... 10
(Parameter data channel 2 ... 10)
z
z
Deactivated
Node guarding, heartbeat
z
1792
700
Boot-up
z
1792
700
Note!
Please observe that the parameter data channels 2 ... 10 are deactivated in the
Lenze setting.
The procedure for activating these parameter data channels is explained in the
description for parameters
to
/
or in the
description for the implemented CANopen object
.