Wiring the installation backplane
Important notes
5
45
EDK94PNE36 DE/EN/FR/ES/IT 2.0
5
Wiring the installation backplane
5.1
Important notes
Danger!
Dangerous voltage
All power terminals remain live for at least three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Wait for at least three minutes before working on the power terminals.
ƒ
Check that all power terminals are deenergised.
Danger!
Dangerous voltage
The discharge current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ
Implement the actions required in the EN 61800-5-1. Especially:
–
Fixed installation
–
PE connection must confirm to standards (PE conductor diameter
≥
10 mm
2
or PE conductor must be connected twice)
Stop!
No device protection in the event of too high mains voltages
The mains input is not fused internally.
Possible consequences:
ƒ
Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ
Observe the max. permissible mains voltage.
ƒ
Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.