Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
83
13
Parameter reference
13.2
Parameters relevant for PROFINET communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13880
C13881
C13885
Parameter | Name:
C13880 | Monitoring Reaction
Data type: UNSIGNED_8
Index: 10695
d
= 29C7
h
The action set in subcode 1 of the code is carried out when the node recognises that it is no longer in the
"Data_Exchange" status.
• Please also observe the notes provided in code
• A change in the monitoring response becomes immediately effective.
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes
Lenze setting
Info
C13880/1
0: No Response
"Watchdog/Data Exchange" monitoring
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13881 | Reaction time delay
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
If the "Data_Exchange" status is exited, the response parameterised in
is activated after the time set here
has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change of monitoring will be effective immediately.
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65535
0 ms
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
This code is used to set the process data which the I/O device is to process in order to maintain the internal
communication when the PROFINET has exited the "Data_Exchange" status.
Selection list
(Lenze setting printed in bold)
0 Use of most recent master PDOs
1 PDOs are set to the value'0'
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT