EDS84DMOTPBUS EN 3.0 - 11/2011
L
29
Communication manual 8400 motec PROFIBUS
Commissioning
Configuring the host (master)
6.2
Configuring the host (master)
For communication with the controller, you have to configure the host (master) first.
Configuration for the host (master) and the DP-V0 parameter data channel
For the configuration of the PROFIBUS, the PROFIBUS device description file of the Inverter
Drive 8400 motec must be read into the master.
The device description file is available on Lenze's website in the "Services & Downloads"
area at:
The following language variants of the device description file can be used:
LENZE84D.GSD (source file, English)
LENZE84D.GSG (German)
LENZE84D.GSE (English)
Defining the user data length
The user data length is defined during the initialisation phase of the master.
The communication unit PROFIBUS supports the configuration of max. 8 process data
words (max. 16 bytes).
The user data lengths for process input data and process output data are the same.