Electrical installation
Important notes
48
EDK84AZESxx DE/EN/FR/ES/IT 5.0
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ
Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ
Observe the maximally permissible mains voltage.
ƒ
Fuse the device correctly on the supply side against mains
fluctuations and voltage peaks.
Stop!
Dangerously high temperatures
The filter is not protected against mains phase failure. In the event
of a mains phase failure, the filter may become very hot.
Possible consequences:
ƒ
Destruction of the device.
ƒ
Smouldering or open fire.
Protective measures:
ƒ
Change the setting for code C00565 from "Warning" to "Fault" or
ƒ
select a wiring for the
bMctrlMainsFault
status output
(
LS_DeviceMonitor
) system block which causes the system to
shutdown within one minute if said output is set to HIGH.