Terminal assignment
EDK82ZAFD 1.0
- 5 -
6mm
0,5...0,6
Nm
4.4...5.3
lb-in
PES
PES
Supply of terminal “Controller inhibit (CINH)” via
external voltage source (X3/20)
X3
6mm
0,5...0,6
Nm
4.4...5.3
lb-in
PES
PES
GND
SH
SH
CH
CH
20
X3
+20V
CL
CL
V-
V-
V+
V+
28
39
7
GND1
E82ZAFDxxx
X3
6mm
0,5...0,6
Nm
4.4...5.3
lb-in
PES
PES
6mm
0,5...0,6
Nm
4.4...5.3
lb-in
PES
PES
Supply of terminal “Controller inhibit (CINH)” via
external voltage source
PES:
HF screen termination by
E82ZAFD003
6mm
0,5...0,6
Nm
4.4...5.3
lb-in
PES
PES
GND
GND1
X3
+20V
_
+
SH
SH
CH
CH
20
CL
CL
V-
V-
V+
V+
28
39
7
HF screen termination by
PE connection
6mm
0,5...0,6
Nm
4.4...5.3
lb-in
PES
PES
Min. wiring required for operation
X3/
Explanation
V-
Reference potential for external voltage supply
CL
CAN-LOW
System bus LOW (data cable)
SH
SHIELD
Shield
CH
CAN-HIGH
System bus HIGH (data cable)
V+
External voltage 24 V DC/ 100 mA
V-
Reference potential for external voltage supply
CL
CAN-LOW
System bus LOW (data cable)
SH
SHIELD
Shield
CH
CAN-HIGH
System bus HIGH (data cable)
V+
External voltage 24 V DC/ 100 mA
7
GND, reference potential
39
GND1, reference potential for X3/28 (CINH)
28
Controller inhibit (CINH)
é
Start = HIGH (+12 V ... +30 V)
é
Stop = LOW (0 ... +3 V)
External terminal supply with
V (ext.) = +12 V DC - 0% ... +30 V DC + 0%
20
+20 V internally for CINH, reference: X3/7
Check whether the bus system is terminated physically at the first and last
participant with R=120 Ohm.