Technical data
Terminal description
Axis modules
l
58
EDS700ACBA EN 5.1
Resolvers are connected to X7 (9−pole Sub−D socket).
The use of third−party resolvers is permissible. For this purpose, the number of pole pairs
of the resolver saved in parameter 0x2C43 (0x3443) must be adapted to the used resolver.
If the stator coils are excited with 4 kHz, the apparent impedance of the connected resolver
must not fall below a value of 65 ohms. If smaller impedances are connected, the overload
protection integrated in the resolver output limits the output current and can falsify the
resolver evaluation.
Resolvers are operated in reverse mode:
ƒ
Supply to the sine and cosine track,
ƒ
Both signals are controlled in a way that the current flow on the reference track is
reduced to zero.
+RE
F
-
RE
F
+CO
S
+
SIN
-SIN
-
CO
S
+
KTY
-KTY
1
2
3
4
5
6
7
8
9
X7
KTY
SSP94RESX7
Fig. 4−2
Wiring principle
Summary of Contents for E70AC Series
Page 1: ...EDS700ACBA Usx Usx Hardware Manual i700 l E70AC Servo Inverter i700 Translation...
Page 2: ...0Fig 0Tab 0...
Page 75: ...Mechanical installation 5 l 75 EDS700ACBA EN 5 1...
Page 147: ...Accessories overview Terminals 11 l 147 EDS700ACBA EN 5 1 E70AZEVK001 i700ZM001 A...
Page 148: ...Accessories overview Terminals 11 l 148 EDS700ACBA EN 5 1 E70AZEVK002 i700ZM001 C...
Page 149: ...Accessories overview Terminals 11 l 149 EDS700ACBA EN 5 1 E70AZEVK003 i700ZM001 B...
Page 150: ...Accessories overview Terminals 11 l 150 EDS700ACBA EN 5 1 E70AZEVK004 i700ZM001 D...
Page 151: ...Accessories overview Terminals 11 l 151 EDS700ACBA EN 5 1 E70AZEVK005 i700ZP005 a...
Page 152: ...Accessories overview Terminals 11 l 152 EDS700ACBA EN 5 1 E70AZEVK006 i700ZP005 b...
Page 161: ......