![Lenze C25BAYCB Operating Instructions Manual Download Page 21](http://html1.mh-extra.com/html/lenze/c25baycb/c25baycb_operating-instructions-manual_1882473021.webp)
5
Appendix
EDBC250SBC |1.1
l
l
l
l
21
5
Appendix
5.1
Technical data (Overview)
5.1.1
System features
General device date
Fieldbus
EtherCAT 100 Mbit/s
Dimensions
25 mm x 120 mm x 90 mm (B x H x T)
Housing mount
aluminium
Shield
connected straight to module housing
Installation
35mm DIN rail (top-hat rail)
IO connection
spring-assisted combi plug with mechanical ejector, 4 … 36-pin
Signal indication
LED located next to the terminal
Diagnosis
LED: bus state, module state, broken wire/excessive current
Number of ports
up to 32 digital I/Os on every module
Supply voltage
24 V DC -20 % / +20 %
Number of I/O modules
20 per bus coupler (total max. power consumption:3A)
Electrical insulation
modules electrically insulated from one another and from the bus
Storage temperature
-25 °C … + 70 °C
Operating temperature
0°C
... + 55 °C
Rel. humidity
5 %
… 95 %, non-condensing
Protection
IP20
Susceptibility to noise
zone B to EN 61131-2, Installation on an earthed top hat rail in the earthed
control
5.1.2
Safety bus coupler
General device date
Part no
13520258
Fieldbus
EtherCAT 100Mbit/s 100 Base TX to IEEE802.3
Connector
2 x RJ45
Controller
ASIC ET1100
Extensions
connection to first Safety Modul integrated in side panel of module
Diagnosis
LED: Modul state
In/Out state