RG-SFMOD
24
Drive Control & Communication
NOTE 6 - AC Tech Register #101, Parameter 51 - Software Version
When parameter #101 is read, the number of points can be 1 or 4. In case of 4 register
read, the drive will send 8 bytes of data back to the MASTER. It does not mean the
read function reads parameter #101, #102, #103, and #104. This is a special case to
handle the ASCII string representing software version. The ASCII string may look like this:
“ SCF6403”. In case of reading one register, received high byte contains software version
and low byte revision number. If received word contains hexadecimal number 0x4003 it
translates to:
0x40 --> decimal 64 (software version) and
0x03 --> decimal 3 (revision number).
NOTE 7 - AC Tech Registers #107 & 108, Parameter 57 & 58 - Digital I/O
Refer to Tables 18 and 19 for the format of AC Tech Registers 107 & 108, Digital I/O.
Digital I/O
Table 18: Register #107 (P57)
Table 19: Register #108 (P58)
Data Low Byte
0
PROTECTION (pin FAULT1)
Data Low Byte
0
1
PROTECTION (pin FAULT2)
1
2
PROTECTION (pin FAULT3)
2
3
FCLIM (pin FAULT4)
3
UP PB
4
STOP (TB1)
4
DOWN PB
5
TB12A
5
PROGRAM PB
6
TB13A
6
7
TB13B
7
FAST CLIM
Data High Byte
8
TB13C
Data High Byte
8
PROTECTION
9
OPEN COLLECTOR TB14
9
10
OPEN COLLECTOR TB15
10
11
CHARGE RELAY
11
12
not used
12
13
not used
13
14
not used
14
15
not used
15