Process data transfer
8.1
Configuring process data (PDO mapping)
62
Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 10.2 EN · 11/2018 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.1
Configuring process data (PDO mapping)
Individual setting of the PDO mapping via the Lenze »Engineer«
The PDO mapping must be set in the »Engineer« if ...
• the "empty application" has been selected in the basic device as a starting point for a technology
application;
• own ports are created for a technology application of the standard device. (Only possible with
activated application in the »FB Editor«.)
Setting PDO mapping with the »Engineer«
Setting of the PDO mapping exclusively via the EtherCAT configuration software
In order that the predefined PDO mapping from the device description file can be used, a standard
technology application must be configured in the standard device. Moreover, the standard ports of
the configured standard technology application must be used.
Stop!
No application must be downloaded in the "Safe-Operational" or "Operational" state,
since the PDO mapping of the EtherCAT master may differ from the PDO mapping of the
inverter (slave).
Note!
In the »Engineer« "Process data object structure: PDO_RX0 / PDO_TX0" dialog, mapping
is not displayed if it has been set exclusively through the EtherCAT-configuration
software.
Configuring the Controller (EtherCAT master)
The current mapping is entered in the mapping codes.