Configuration
2−132
l
EDSVF9383V−EXT EN 2.0
2.4.45
Blocking frequencies (NLIM)
This FB blocks signals in max. three speed ranges which can be defined. The output signal skips the
defined ranges. If you use the output signal as setpoint speed, the motor only passes the blocked
ranges.
NLIM1
NLIM1−OUT
NLIM1−IN
C0511
C0038/5
C0510
C0038/3
C0038/1
C0038/6
C0038/4
C0038/2
Fig. 2−104
Blocking frequencies (NLIM1)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
NLIM1−IN
a
C0511
dec [%]
C0510
1
1000
−
NLIM1−OUT
a
−
−
−
−
−
−
Function
A blocked speed range is activated by entering a lower and an upper speed limit.
The output signal remains at the lower limit of the block range until the input signal has over− or
undershot the blocked speed range.
Code
Choice
Function
C0038/1
0 {1
rpm}
36000
0 = Function not active
Blocked speed range 1
defines the lower limit
C0038/2
defines the upper limit
C0038/3
Blocked speed range 2
defines the lower limit
C0038/4
defines the upper limit
C0038/5
Blocked speed range 3
defines the lower limit
C0038/6
defines the upper limit
-C0038/2
C0011
C0038/3
C0011
-C0038/1
C0011
C0038/4
C0011
NLIM1-IN
NLIM1-OUT
Fig. 2−105
Representation of the upper and lower limits of the blocked speed ranges
Blocked speed range 1
Blocked speed range 2