
Safety option 20
Safe parameter setting
Parameter setting
l
27
EDS84DPSO01 EN 2.1
4.7
Safe parameter setting
)
Note!
Safety−relevant parameters can exclusively be transmitted to the drive−based
safety by safe parameter setting using the »Engineer«.
The parameter set is saved to the memory module and the drive−based safety
with a definite module ID which must comply with the effective safety address
in the drive−based safety.
The following is required for the parameterisation and configuration of the safety option:
ƒ
A computer with a Windows® operating system (XP or 2000)
ƒ
The Lenze »Engineer« PC software
ƒ
Connection with the controller via an interface.
– diagnostic interface X70 with diagnostic USB adapter
– PROFINET
– Ethernet
Further information and help can be found in:
ƒ
the online help of the controller with safety option
ƒ
the 8400 protec software manual, integrated safety system ...,
order designation: EDS84DWTSO
4.7.1
Parameter setting
Safety−relevant parameters can exclusively be transmitted to the drive−based safety by
safe parameter setting. The parameter set is saved to the memory module and the
drive−based safety with a definite module ID which must comply with the effective safety
address in the drive−based safety.
Safe parameter setting requires the service status. The service status means:
ƒ
The standard stop is active and the drive is safely switched to torqueless operation
(STO).
ƒ
The communication via the safety bus is active but passivated.
About the service status:
ƒ
It can be activated by the Lenze »Engineer« PC software.
ƒ
It can be quit by reinitialising the drive−based safety, i.e. the communication via the
safety bus is interrupted.
)
Note!
The service status also occurs if the parameter set in the memory module does
not comply with the parameter set in the drive−based safety during
initialisation.