Electrical installation
Wiring according to EMC
5
EDK82ZMFBC-001 DE/EN/FR 7.0
49
H1_E_INST-INS_Klemmenbeleg
5
Electrical installation
Wiring according to EMC
Please observe the following for wiring according to EMC guidelines:
Note!
ƒ
Separate control cables from motor cables.
ƒ
Lead the shields as far as possible to the terminals (unshielded core length
< 40 mm).
ƒ
Connect control and data cable shields as follows:
–
Analog
signal cable shields must be connected
with one end
at the
inverter.
–
Digital
signal cable shields must be connected
with both ends
.
ƒ
More information about wiring according to EMC guidelines can be
obtained from the corresponding documentation for the standard device.
How to connect the shield
c
d
e
8200mot045/046/047
1. Prepare cable.
2. Insert cable tie into shield sheet.
3. Insert cable and tighten cable tie. Shield and shield sheet must be tightly connected.