Commissioning
5-2
L
BA2102EN
Next steps for 93XX
1. Now you can communicate with each drive, i.e. you can read all codes and change all
writeable codes.
2. Set the Lenze parameter signal configuration (C0005) to a value xxx1 to control the controller.
For the first commissioning, select the signal configuration 1011 (speed control).
3. Terminal 28 (ctrl. enable=controller enable) is always active and must be on HIGH level during
operation (see Operating Instructions 93XX). Otherwise, the controller cannot be enabled.
–
With the signal configuration C0005=1011, the QSP function (quick stop) and the CW/CCW
changeover are assigned to the input terminals E1 and E2, and thus they are always active.
During operation, E1 must be at HIGH level (see Operating Instructions 93XX).
Tip!
With the signal configuration C0005=xx11, terminal A1 is switched as voltage output. Thus, only the
following terminals can be connected via cables:
X5.A1 with X5.28 (ctrl. enable)
X5.A1 with X5.E1 (R/QSP)
4. With signal configuration 1011 (speed control), the speed setpoint can be selected in % of
n
max
under C0141.