19
CMVLC401A
Commissioning
8
Drive Registers
8.1
Configuration and Control Registers
Registers #1 through #1099 are reserved for registers that are only available over the network and cannot be accessed
via the drive’s local keypad.
Table 9: Configuration & Control Registers
Code
Number
Parameter Name
Default Range of Adjustment
Important
C0040
Controller Inhibit
0
0 Controller inhibited
1 Controller enabled
The controller can also be enabled
with the control word C0135
C0043
Fault Reset
0
0 No Action
1 Reset Fault
The fault can also be reset with
the control word C0135
C0046
Frequency Setpoint
0.0
…
500.0 Hz
Read only
C0050
Actual Output
Frequency
0.0
…
500.0 Hz
Read only
C0068
Operating Status Bit
Word
Bit
Description
Read only
0-3
The 10th digit of the LECOM fault number is
displayed. Example:
TRIP OH = 5 (LECOM no. = 50)
4-7
Last communication error
0 = No fault
1 = Check sum error
2 = Protocol frame error
3 = Reserved
4 = Invalid code number
5 = Invalid variable
6 = No access permission
7 = Telegram processing interrupted by a new
telegram
15 = General fault
8
Control via LECOM enabled
9
Actual frequency above threshold C17
10
Direction of rotation
0 = CW
1 = CCW
11
Power stage transistors energized
12
Quick STOP active
13
Current Limit
14
Setpoint frequency reached
15
Fault occurred
LECOM Format = VH