Chapter 3. Replacing a fan
You can replace a failed fan nondisruptively in an DM240N drive shelf that is powered on, and while I/O is in
progress.
Before you begin
• All other components in the system, including the other four fans, must be functioning properly.
• You must have verified that the shelf containing the failed FRU is cabled correctly, by downloading and
running ThinkSystem Intelligent Monitoring Config Advisor. If any cabling errors are generated, follow the
corrective actions provided.
Lenovo Downloads: ThinkSystem Intelligent Monitoring Config Advisor
About this task
• Allow at least 70 seconds between removal and installation of the NVMe shelf module (NSM).70 seconds
is the time it takes for ONTAP to recover: clean up the data structures and the driver to register the shelf ID
correctly.
•
Best practice:
The best practice is to have current versions of NVMe shelf module (NSM) firmware and
drive firmware on your system before replacing FRU components.
Note:
Do not revert firmware to a version that does not support your shelf and its components.
Lenovo Downloads: Disk Shelf Firmware
Lenovo Downloads: Disk Drive and Firmware
• If needed, you can turn on the shelf's location (blue) LEDs to aid in physically locating the affected shelf:
storage shelf location-led modify -shelf-name
shelf_name
-led-status on
If you do not know the
shelf_
name
of the affected shelf, run the
storage shelf show
command.
A shelf has three location LEDs: one on the operator display panel and one on each NSM module.
Location LEDs remain illuminated for 30 minutes. You can turn them off by entering the same command,
but using the off option.
• When you unpack the replacement fan, save all packing materials for use when you return the failed fan.
You return the failed part to Lenovo as described in the RMA instructions shipped with the kit. If you need
the RMA number or additional help with the replacement procedure, contact technical support at
, 888-463-8277 (North America), 00-800-44-638277 (Europe), or +800-800-80-800 (Asia/Pacific).
A video for this task is available at:
• Youtube: https://www.youtube.com/playlist?list=PLYV5R7hVcs-BhZmHgn868u8QatfgH8JW4
• Youku: https://list.youku.com/albumlist/show/id_52419127
Step 1. Properly ground yourself.
Step 2. Disconnect the cabling from the NSM module that contains the FRU that you are replacing:
a. Disconnect the power cord from the power supply by opening the power cord retainer, and
then unplug the power cord from the power supply. Power supplies do not have a power
switch.
b. Disconnect the storage cabling from the NSM module ports. Make a note of the NSM module
ports that each cable is connected to. You reconnect the cables to the same ports when you
reinsert the NSM module, later in this procedure.
Step 3. Remove the NSM module from the shelf:
© Copyright Lenovo 2020
7
Summary of Contents for ThinkSystem DM240N
Page 1: ...Service Guide for DM240N ...
Page 4: ...ii Service Guide for DM240N ...
Page 8: ...4 Service Guide for DM240N ...
Page 14: ...10 Service Guide for DM240N ...
Page 18: ...14 Service Guide for DM240N ...
Page 22: ...18 Service Guide for DM240N ...
Page 28: ...24 Service Guide for DM240N ...
Page 30: ...26 Service Guide for DM240N ...
Page 33: ......
Page 34: ......