Note:
The UPS charges the battery packs as soon as it is connected to the
AC-power source, even if the
button is not pressed.
Procedure
1.
Connect the UPS input socket
to the AC-power source using the cable of
the protected equipment. Connect a 250 V - 16 A cable to the socket
, then to
the AC-power source.
2.
Connect the loads to the UPS using the cables
. It is preferable to connect
the priority loads to the four outlets marked (9) and the non-priority loads to
the four outlets marked
that can be programmed in pairs (1 and 2).
For the 2AX, 2KX, 3AX, and 3KX models, connect any high-power devices to
the 16 A outlet
.
To program shutdown of outlets
during operation on battery power to
optimize the available backup time, check the in/out settings (described in
Table 1 on page 13).
3.
Fit the connection securing system
that prevents the plugs from being
pulled out accidentally.
What to do next
After the UPS is connected to the AC power source, eight hours of charging is
required before the battery packs can supply the rated backup time.
Installing the Extended Battery Module (EBM)
Machine Types and Models
Weights (kg/lb)
Dimensions (mm/inch) D x
W x H
5594-2BX
72.30
/ 32.80
20.6 x 17.4 x 3.4
/ 522 x 441.2
x 86.2
5594-3BX
102.3
/ 46.39
25.5 x 17.4 x 3.4
/ 647 x 441.2
x 86.2
24
Installation and User's Guide
Summary of Contents for RT1.5kVA
Page 1: ...2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide ...
Page 2: ......
Page 3: ...2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide ...
Page 6: ...iv Installation and User s Guide ...
Page 20: ...4 Installation and User s Guide ...
Page 34: ...18 Installation and User s Guide ...
Page 52: ...36 Installation and User s Guide ...
Page 56: ...40 Installation and User s Guide ...
Page 60: ...44 Installation and User s Guide ...
Page 72: ...56 Installation and User s Guide ...
Page 74: ...58 Installation and User s Guide ...
Page 75: ......
Page 76: ...Part Number 00WA359 Printed in USA 1P P N 00WA359 ...