Procedure
Step 1. Install the drive backplane.
Figure 29. Installing the drive backplane
Align the tabs on the bottom of the drive backplane with the slots on the system board, and
insert them into the slots.
Push the top of the drive backplane forward until it clicks in place.
After this task is completed
Proceed to complete the parts replacement (see “Complete the parts replacement” on page 218).
Install a 2.5-inch hot-swap drive
Follow instructions in this section to install a 2.5-inch hot-swap drive.
About this task
Attention:
• Go over “Installation Guidelines” on page 107 to ensure that you work safely.
Notes:
The server supports up to three drive backplanes with the following corresponding drive bay
numbers.
Figure 30. Drive backplane numbering
.
Hardware replacement procedures
113
Summary of Contents for 7D31
Page 1: ...ThinkSystem SR850 V2 Maintenance Manual Machine Types 7D31 and 7D32 ...
Page 8: ...vi ThinkSystem SR850 V2 Maintenance Manual ...
Page 52: ...44 ThinkSystem SR850 V2 Maintenance Manual ...
Page 60: ... Three backplanes on page 57 52 ThinkSystem SR850 V2 Maintenance Manual ...
Page 70: ...62 ThinkSystem SR850 V2 Maintenance Manual ...
Page 71: ...Chapter 3 Internal cable routing 63 ...
Page 78: ...70 ThinkSystem SR850 V2 Maintenance Manual ...
Page 114: ...106 ThinkSystem SR850 V2 Maintenance Manual ...
Page 236: ...Figure 133 System board and expansion board LEDs 228 ThinkSystem SR850 V2 Maintenance Manual ...
Page 258: ...250 ThinkSystem SR850 V2 Maintenance Manual ...
Page 260: ...252 ThinkSystem SR850 V2 Maintenance Manual ...
Page 264: ...256 ThinkSystem SR850 V2 Maintenance Manual ...
Page 273: ......
Page 274: ......