Page 33
XP16
Table 1 − HFC−410A Normal Operating Pressures (Liquid
+
10 & Suction
+
5 psig) (XP16−XXX−230−04)
*Temperature
of the air
entering the
outdoor coil.
Model
−024
−036
−048
−060
−036
°F (°C)*
Liquid Line Pressure/Vapor Line Pressure
Cooling
First Stage
(Low Capacity)
65 (18)
232
/
146
225
/
144
235
/
144
225
/
138
75 (24)
264
/
148
261
/
147
268
/
145
264
/
141
85 (29)
307
/
149
302
/
149
310
/
147
305
/
142
95 (35)
353
/
151
349
/
151
356
/
148
352
/
146
105 (41)
403
/
153
397
/
153
407
/
150
405
/
148
115 (45)
460
/
155
461
/
157
466
/
152
459
/
150
Cooling
Second Stage
(High
Capacity)
65 (18)
240
/
143
239
/
139
244
/
140
241
/
134
75 (24)
279
/
145
278
/
141
283
/
141
280
/
136
85 (29)
322
/
147
322
/
143
326
/
144
324
/
137
95 (35)
371
/
149
367
/
146
374
/
147
373
/
138
105 (41)
423
/
151
426
/
148
427
/
148
425
/
142
115 (45)
485
/
154
489
/
151
491
/
151
486
/
146
Heating
First Stage
(Low Capacity)
50 (10)
333
/
116
318
/
116
354
/
115
365
/
113
40 (4.5)
314
/
88
304
/
89
324
/
92
341
/
89
Heating
Second Stage
(High Capac-
ity)
50 (10)
346
/
109
333
/
110
370
/
110
369
/
107
40 (4.5)
321
/
89
314
/
88
345
/
92
348
/
86
30 (−1)
303
/
74
303
/
77
322
/
70
335
/
73
20 (−7)
286
/
59
289
/
63
305
/
61
318
/
59