background image

7

Refrigerant Piping Connections

Field piping consists of two copper lines connected to the 

indoor unit. Table 1 lists the connection sizes at the indoor 

unit. The connections are made using the provided brass 

flare nuts at the end of the refrigerant piping connections. 

Both lines must be individually insulated.

1.  The seal on the unit refrigerant piping connections 

should remain in place until the last possible moment. 

This will prevent dust or water from getting into the 

refrigerant piping before it is connected.

2.  CAREFULLY adjust refrigerant piping connections to 

suit the application (straight back, right or left).

3.  Slowly  loosen  one  of  the  flare  nuts  to  release  the 

factory nitrogen charge.

4.  Remove  the  flare  nuts  from  the  connections  on  the 

unit and discard the seal from each of the piping 

connections.

5.  Slide the flare nuts onto the ends of the field-provided 

refrigerant piping 

before

 using a suitable flaring tool 

to flare the end of the copper pipe.

6.  Apply  recommended  HFC-410A  refrigerant  lubricant 

to  the  outside  of  the  flared  refrigerant  lines  (figure 

7-A). 

Size 

(Btuh)

Liquid Line 

in.

Vapor Line 

in.

7000
9000

12000
15000

1/4

1/2

18000
24000
30000

3/8

5/8

Table 1. Refrigerant Piping Connections

7.  Align  the  threaded  connections  with  the  flared 

refrigerant lines. Tighten the flare nuts lightly at first to 

obtain a smooth match (figure 7-B).

8.  Once snug, continue another half-turn on each nut 

which should create a leak-free joint. A torque wrench 

may  be  used  to  tighten  flare  nuts  using  table  2 

recommendations. See figure 4. 

Do not over-tighten 

a flared joint. Flared connections should always 

be accessible and must be insulated to prevent 

condensation.

9.  After refrigerant piping has been installed and checked 

for leaks, apply insulation over the connector pipe and 

all flared connections.

A

B

CANT ON THE OUTSIDE OF

THE FLARE

MALE FLARE

CONNECTION

Figure 7. Making Connections 

(Male to Female Connection)

Figure 8. Tighten Flare Nut

To Indoor Unit

Torque Wrench

Backup
Wrench

To Outdoor Unit

 IMPORTANT

The compressor in this unit contains PVE 

oil  (Polyvinylether).  PVE  oil  is  formulated  for  

hydrofluorocarbon (HFC) refrigerants, such as R-410a, 

which this system contains. While it may have some 

miscibility properties with mineral-based oil and POE oil 

(Polyolester), it is not recommended to mix PVE oil with 

any other type of refrigerant oil.

 IMPORTANT

Always use two wrenches when tightening flare nuts to 

avoid twisting refrigerant piping. DO NOT over-tighten 

flare nuts.

Refrigerant leaks are unlikely; however, if a refrigerant 

leak occurs, open a door or windows to dilute the 

refrigerant  in  the  room. Turn  off  the  unit  and  all  other 

appliances that may cause a spark. Call a licensed 

professional HVAC technician (or equivalent) to repair 

the leak. 

Use only R410A refrigerant to charge this system. Use 

of  other refrigerant or gas will damage the equipment.

Do not allow air or other contaminants to enter system 

during installation of refrigerant piping. Contaminants 

will result in lower system capacity and abnormally high 

operating pressures and may result in system  failure or 

explosion.

Insulate all refrigerant piping.

Refrigerant pipes may be very hot during unit operation. 

Do not allow contact between wiring and bare copper 

pipes. 

After refrigerant piping connections have been 

completed, check the system for leaks per  commissioning 

instructions.

 WARNING

Summary of Contents for VRF VWMB Series

Page 1: ...injury or loss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow safety warnings and these instruc tio...

Page 2: ...se of a different rating Do not use a jumper wire to replace a fuse Do not insert your hands tools or any other item into the air intake or air outlet at either the indoor or outdoor unit Do not allow...

Page 3: ...879 39 991 12 3 8 314 7 1 2 191 4 1 2 114 VWMB007H4 VWMB009H4 VWMB012H4 VWMB015H4 VWMB018H4 27 686 BOTTOM VIEW SIDE VIEW SIDE VIEW 8 7 8 225 42 1 2 1080 47 1194 13 1 2 343 10 3 8 264 VWMB024H4 VWMB030...

Page 4: ...t of the unit Install the indoor unit a minimum of 3 feet away from any antenna power cord line radio telephone security system or intercom Electrical interference and radio frequencies from any of th...

Page 5: ...e installed level on the wall to allow proper condensate drainage 1 Use a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate t...

Page 6: ...of copper pipe and wiring can deteriorate when exposed to these construction materials USE SUITABLE TOOL TO CUT PVC FOR WALL SLEEVE AT SLIGHT ANGLE AS SHOWN Figure 4 Cutting PVC for Wall Sleeve Insta...

Page 7: ...connections should always be accessible and must be insulated to prevent condensation 9 After refrigerant piping has been installed and checked for leaks apply insulation over the connector pipe and a...

Page 8: ...ll drain freely 4 After system installation is complete the condensate drain line must be checked for leaks This check is part of the commissioning sequence If a field provided condensate pump has bee...

Page 9: ...X87 721 14T69 3 7 23 16 5 ft VWMB024H4 VWMB030H4 MaxiBlue w DrainStik X87 722 17A23 3 7 23 16 5 ft Optional pump maximum suction lift is measured from the pump outlet Table 3 Condensate Pump Accessory...

Page 10: ...tdoor Unit Main Unit L1 L2 L3 Outdoor Unit Sub1 unit L1 L2 L3 Outdoor Unit Sub2 Unit L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 Service Disconnect Service Disconnect Service Discon...

Page 11: ...olarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Un...

Page 12: ...agram VRF Heat Pump System NOTE PQE Communication wiring is daisy chained from the outdoor unit to each indoor unit in one continuous run Tightening torque for the terminal screws Use the correct scre...

Page 13: ...WIRING Display panel To Outdoor COMM BUS To wired Controller COMM BUS HA HB COM P 12V Q GRAY YELLOW BLUE WHITE BLACK RED HHE interface FAN CTON HTON AUXH NET0 NET1 Current range 0 1A Voltage range 0...

Page 14: ...HITE BLACK RED NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING NOTE 1 REFER TO MANUAL FOR COMMUNICATION WIRING 2 PLEASE USE THE 3 CONDUCTOR SHIELDED CABLE T2A T2 T1 T2B RED WHITE BLUE BLACK Di...

Page 15: ...le Spot Check Instructions This Spot Check Performance table is located on the unit service panel The diagnostic information can also be obtained using the wired remote controller No Content Recorded...

Page 16: ...codes The error code will replace the temperature setting displayed on the receiver If more than one error has occurred the codes will alternate so that all codes are shown Figure 32 Receiver Display...

Page 17: ...17 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: