background image

18

Cassette Cover Panel Installation

1.  Carefully remove the cassette cover panel from its 

protective  packaging  and  place  the  panel  diffuser-

side-out on a clean, level surface.

Cover Panel

Swing motor installation cover

2

3

Cover

Steel  rope

1

3

Drain side

Make note of the arrows to 
ensure proper installation of 
cover. If impropery installed, 
cover cannot be easily 
removed in the future.

Latch Release Tabs

45º

Slide tabs toward each

other to release latch.

Tilt return air grille outward,

then, lift to remove grille

from panel.

≥7/8 (22 mm)

1-7/8 (48 mm)

⅜”

Threaded

Rod

Cassette

Unit 

Base

Cover

 

Panel

Ceiling

Leveling

Nut

air ou

t

Cassette Bas

e

Ceiling

Foam

Insulation

Cover

 

Panel

Suppl

y Ai

r

Louver

Foam

Insulation

Side View Cutaway

Panel

Foam

Insulation

Figure 23. Remove Return Air Grille

 

 CAUTION

Do not place the cover panel with the diffusers face down 

on the floor or other surface. Louvers will be damaged if 

pressure is applied to them.

2.  Slide the two grille latches toward each other at the 

same time to release the grille. See Figure 24. Tilt the 
return air grille outward at a 45º angle (grille is held 

in place by tethers). Release the tethers and lift the 

grille away from the panel. Carefully place the return 

air grille off to the side. 

3.  Position the ceiling panel so that the arrow on the 

panel is aligned with the arrow sticker on the cassette 
base (both arrow stickers should be on the same 

side of the cassette base). 

NOTE - If the panel and 

the base are not properly aligned, the airflow will be 

blocked and the harness plugs from the panel to the 
cassette base will not be long enough to plug together. 

See Figure 24.

4.  Connect the six-pin harness plugs from each of the 

two swing motors to the matching six-pin plugs from 
the control box in the cassette base.

5.  Connect the black harness from the display on the 

cover panel to the corresponding black plug from the 
control box in the cassette base.

6. 

Connect the return air sensor (behind the filter) on the 

cover panel to the corresponding white plug from the 
control box in the cassette base.

7.  Adjust the cover panel by turning slightly clockwise, 

if necessary, to make sure that the panel is properly 
aligned with the cassette base.

8.  Use the provided screws to secure the cover panel 

to the unit base. Continue to tighten the cover panel 
securing screws until the insulation between the cover 
panel and the cassette base has been compressed to 

approximately ¼” (6 mm). The cover panel must form 

a seal with the ceiling and the cassette base around 
the entire perimeter of the unit. See Figure 25.

9.  If it is necessary to adjust the cassette height after the 

cover panel has been installed, access the leveling 
nut through the return air grille opening.

10.  The return air grille is tethered to the cover panel and 

must be reinstalled. Align the four tabs on the grille 
with the four slots in the cover panel. Tilt the panel 
back into place. Press the opposite side of the cover 
gently until the latches engage.

Figure 24. Install Panel Cover

Figure 25. Cover Panel In Place

NOTE - Cover panel must be ordered as a separate accessory. 

 IMPORTANT

Connect the return air sensor on the cover panel to the 
white plug in the control box.

.

Summary of Contents for VRF V22A Series

Page 1: ...persede local codes in any way Consult authorities having jurisdiction before installation WARNING Improper installation adjustment alteration ser vice or maintenance can cause property damage persona...

Page 2: ...voided NOTE Only Lennox VRF indoor units will work with Lennox VRF outdoor units and associated mechanical equipment Lennox Mini Split indoor units are similar in appearance but must not be connected...

Page 3: ...NNECTION 2 3 8 60 LIQUID PIPE GAS PIPE 20 1 2 521 Hook Location 22 5 8 575 Body 25 1 2 648 Panel 21 1 2 545 Hook Location 22 5 8 575 Body 25 1 2 648 Panel 10 3 8 264 2 51 ELECTRONIC EXPANSION VALVE DR...

Page 4: ...the weight of the unit the unit could be fall out of place and cause serious injury Use the provided and specified components when installing equipment Failure to do so may result in unit falling wat...

Page 5: ...securely in place to accept the threaded rods NOTE Threaded rod requirement of Lennox warranty program is the ONLY acceptable method of suspending the unit do not use chains or straps See Figure 1 L t...

Page 6: ...piping before it is connected 2 Slowly loosen one of the flare nuts to release the factory nitrogen charge 3 Remove the flare nuts from the connections on the unit and discard the seal from each of th...

Page 7: ...red connections should always be accessible and must be insulated to prevent condensation Outside Diameter Recommended Torque No torque wrench available Finger tighten and use an appropriately sized w...

Page 8: ...1 4 inch per foot and that each individual drain is connected to the main drain exactly as shown 5 Drain should be as short as possible and should not have any droops or kinks that would restrict con...

Page 9: ...m circuit ampacity and maximum overcurrent protection size 1 Remove the screws that secure the control box cover Remove the cover and place it to the side where it will not be damaged CAUTION This uni...

Page 10: ...L1 L2 L3 L1 L2 L1 L2 Single Phase power wiring PQE PQE Indoor units and MS boxes on the same refrigeration circuit should have a common power supply but must have an independent disconnect switch ins...

Page 11: ...11 Figure 11 Typical Communication Wiring Diagram VRF Heat Recovery System NOTE Each communication wire from the MS box should follow the refrigerant piping for that port...

Page 12: ...not be properly tightened If the terminal screws are over tightened screws might be damaged Refer to the table below for the tightening torque of the terminal screws After wiring confirm all connecti...

Page 13: ...LEVEL SWITCH CS T2B T2 TR FM XS1 9 XP1 9 T1 C KEY XT1 2 EEV COMPONENT INDOOR FAN ELECTRONIC EXPANSION VALVE INLET AIR TEMP COIL TEMP FAN CAPACITOR TRANSFORMER TERMINAL BLOCK EVAP OUTLET TEMP IN COOLIN...

Page 14: ...shown Figure 14 Typical Outside Air Diverter Remove Screw Figure 16 Typical Outside Air Supply Channel with Styrofoam Plug Removed 3 Make sure the outside air supply channel is clear of styrofoam and...

Page 15: ...nstalled 2 Identify and measure the supply air opening that will be blanked off See figure 18 3 Prepare the blocking material Cut a piece of styrofoam or other non conductive material to fit the suppl...

Page 16: ...16 Figure 19 Three way Outlet Possible Flow Patterns Figure 20 Two way Outlet Possible Flow Patterns...

Page 17: ...the duct knockouts can be used 1 Decide which side of the cassette body will be ducted 2 Seal the supply air outlet on the side to which the duct will be attached See the Supply Air Configurations se...

Page 18: ...flow will be blocked and the harness plugs from the panel to the cassette base will not be long enough to plug together See Figure 24 4 Connect the six pin harness plugs from each of the two swing mot...

Page 19: ...1 7 The middle evaporator temperature T2 8 The evaporator outlet temperature T2B 9 Error code 10 Use the Spot Check Performance tables below and the Manual button on the unit receiver to view diagnost...

Page 20: ...ing mode Timer LED is Active Fan coil is under timer control Operation And Timer LED Flash Fast Fan coil unit has no registered address upon receiving a power supply Timer LED Flashes Fast Communicati...

Page 21: ...21 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: