Table 9. VRB Electrical Data
Model No.
VRB072H4
VRB096H4
VRB120H4
Line voltage data - 60 hz - 3 phase
208/230V
460V
208/230V
460V
208/230V
460V
1
Maximum Overcurrent Protection (amps)
50
30
60
30
60
30
2
Minimum circuit ampacity
49.9
26.8
52.4
28.2
54.2
29.5
Compressor
No. of compressors
1
1
1
1
1
1
Rated load amps
35.5
19
37
20
38.5
21
Outdoor Fan
Motor
Motor type
DC
DC
DC
DC
DC
DC
No. of motors
2
2
2
2
2
2
Full load amps
2.6/2.9
1.4/1.6
2.9/3.2
1.5/1.7
2.9/3.2
1.5/1.7
Input - W 680/780
750/850
780/890
820/930
780/890
820/930
Output - W 580/660
640/720
670/760
700/800
670/760
700/800
Model No.
VRB144H4
VRB168H4
VRB192H4
Line voltage data - 60 hz - 3 phase
208/230V
460V
208/230V
460V
208/230V
460V
1
Maximum Overcurrent Protection (amps)
80
40
90
40
90
40
2
Minimum circuit ampacity
77.1
37.4
84.8
39
85.4
39.6
Compressor
No. of compressors
2
2
2
2
2
2
Rated load amps
31/30
15/14
34/34
15.5/15
34.5/34
16/15
Outdoor Fan
Motor
Motor type
DC
MOTOR
DC
MOTOR
DC
MOTOR
DC
MOTOR
DC
MOTOR
DC
MOTOR
No. of motors
2
2
2
2
2
2
Full load amps
4.0/4.3
2.2/2.4
4.0/4.3
2.2/2.4
4.0/4.3
2.2/2.4
Input - W 1200/1200 1200/1200 1200/1200 1200/1200 1200/1200 1200/1200
Output - W 900/940
900/940
900/940
900/940
900/940
900/940
NOTES:
In multiple module systems each outdoor unit requires a separate electrical connection.
Incoming voltage must not be above or below these voltage ranges: 208/230V - 191V minimum, 247V maximum; 460V - 423V minimum , 497V
maximum. 2% Maximum line voltage tolerance between phases.
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.