TAA090 BLOWER PERFORMANCE
All data is measured external to the unit with dry coil and standard 2 in. air filters in place.
FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any field installed accessories air resistance (electric heat, economizer, etc.) See page 13.
Then determine from table the blower motor hp and drive rpm required. See page 12 for blower drive specifications.
Air
Volume
cfm
STATIC PRESSURE EXTERNAL TO UNIT − Inches Water Gauge
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
RP
M
BHP
RP
M
BHP
RP
M
BHP
RP
M
BHP
RP
M
BHP
RP
M
BHP
RP
M
BHP
RP
M
BHP
1600
430
0.52
485
0.62
539
0.71
590
0.77
636
0.83
680
0.88
721
0.94
758
0.99
1700
439
0.55
494
0.65
548
0.74
599
0.80
645
0.86
688
0.91
729
0.97
766
1.03
1800
448
0.58
503
0.68
558
0.77
608
0.83
654
0.89
697
0.95
737
1.01
774
1.08
1900
457
0.62
513
0.72
567
0.80
617
0.86
663
0.93
705
0.99
745
1.06
781
1.12
2000
467
0.65
523
0.75
577
0.83
627
0.90
672
0.96
714
1.03
753
1.10
789
1.17
2100
477
0.68
533
0.78
587
0.86
637
0.93
681
1.00
723
1.08
762
1.15
797
1.22
2200
487
0.72
543
0.82
597
0.90
646
0.97
691
1.05
732
1.12
770
1.20
805
1.27
2300
497
0.75
554
0.85
608
0.94
657
1.01
700
1.09
741
1.17
779
1.25
813
1.32
2400
508
0.79
565
0.89
619
0.98
667
1.06
710
1.14
750
1.23
787
1.30
822
1.38
2500
519
0.83
577
0.94
630
1.02
677
1.10
720
1.19
759
1.28
796
1.36
830
1.43
2600
531
0.87
588
0.98
641
1.07
688
1.16
729
1.25
769
1.34
805
1.42
839
1.49
2700
543
0.92
600
1.03
653
1.12
698
1.21
739
1.31
778
1.40
814
1.48
848
1.55
2800
555
0.97
613
1.08
664
1.17
709
1.27
749
1.37
788
1.46
824
1.54
857
1.62
2900
568
1.02
625
1.13
676
1.22
719
1.32
759
1.43
797
1.52
833
1.60
866
1.68
3000
581
1.07
638
1.18
687
1.28
730
1.39
769
1.49
807
1.58
842
1.67
875
1.75
3100
595
1.12
651
1.24
699
1.34
740
1.45
779
1.56
817
1.65
852
1.73
883
1.82
3200
609
1.18
664
1.30
710
1.41
751
1.52
789
1.63
827
1.72
861
1.80
892
1.89
3300
624
1.24
677
1.36
722
1.48
761
1.59
799
1.70
836
1.79
870
1.88
901
1.97
3400
639
1.30
690
1.43
733
1.55
772
1.67
810
1.77
846
1.86
879
1.95
909
2.05
3500
653
1.37
703
1.50
745
1.62
782
1.75
820
1.85
856
1.94
888
2.03
917
2.14
3600
668
1.44
715
1.57
756
1.70
793
1.83
830
1.93
865
2.02
897
2.12
925
2.24
Air
Volume
cfm
STATIC PRESSURE EXTERNAL TO UNIT − Inches Water Gauge
0.9
1.0
1.1
1.2
1.3
1.4
1.5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1600
793
1.05
826
1.1
859
1.15
891
1.21
923
1.27
952
1.34
981
1.42
1700
800
1.09
833
1.15
866
1.20
899
1.26
930
1.33
959
1.40
987
1.48
1800
807
1.13
840
1.19
873
1.25
906
1.31
936
1.38
966
1.46
994
1.54
1900
815
1.18
848
1.24
881
1.30
913
1.36
943
1.44
972
1.52
1000
1.60
2000
823
1.23
856
1.29
889
1.35
921
1.42
951
1.50
979
1.58
1007
1.67
2100
830
1.28
863
1.34
896
1.40
928
1.48
958
1.56
986
1.65
1013
1.74
2200
838
1.33
871
1.39
904
1.46
935
1.54
965
1.63
993
1.72
1020
1.81
2300
846
1.39
880
1.45
912
1.52
943
1.61
972
1.70
999
1.79
1026
1.88
2400
855
1.44
888
1.51
920
1.59
950
1.67
979
1.77
1006
1.86
1033
1.96
2500
863
1.50
896
1.57
928
1.65
958
1.74
986
1.84
1013
1.94
1039
2.04
2600
872
1.56
904
1.64
936
1.72
965
1.82
993
1.92
1019
2.02
1045
2.12
2700
880
1.62
913
1.70
943
1.79
972
1.89
1000
2.00
1026
2.10
1052
2.20
2800
889
1.69
921
1.77
951
1.87
979
1.97
1006
2.08
1033
2.18
1058
2.29
2900
898
1.76
929
1.85
959
1.95
987
2.05
1013
2.16
1039
2.26
1064
2.37
3000
906
1.83
937
1.93
966
2.03
994
2.13
1020
2.24
1046
2.35
1070
2.46
3100
914
1.91
944
2.01
973
2.11
1001
2.22
1027
2.33
1052
2.44
1077
2.55
3200
922
1.99
952
2.09
980
2.20
1008
2.30
1033
2.41
1058
2.53
1083
2.64
3300
930
2.07
959
2.18
987
2.29
1014
2.39
1040
2.50
1065
2.62
1089
2.73
3400
938
2.16
966
2.27
994
2.38
1021
2.49
1046
2.60
1071
2.71
1095
2.83
3500
945
2.26
973
2.37
1001
2.48
1028
2.58
1053
2.69
1077
2.81
1101
2.93
3600
953
2.35
980
2.47
1008
2.58
1034
2.68
1059
2.79
1084
2.91
1107
3.03