Lennox TAA Series Unit Information Download Page 10

Page 10

TAA240 BLOWER PERFORMANCE

All data is measured external to the unit with dry coil and standard 2 in. air filters in place.
FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any field installed accessories air resistance (electric heat, economizer, etc.) See page 14.
Then determine from table the blower motor hp and drive rpm required. See page 12 for blower drive specifications.

Air

Volume

cfm

STATIC PRESSURE EXTERNAL TO UNIT − Inches Water Gauge

0.1

0.2

0.3

0.4 

0.5

0.6

0.7 

0.8 

RP

M

BHP

RP

M

BHP

RP

M

BHP

RP

M

BHP

RP

M

BHP

RP

M

BHP

RP

M

BHP

RP

M

BHP

4400

449

1.05

493

1.22

539

1.38

584

1.52

628

1.68

670

1.85

711

2.04

748

2.24

4600

456

1.11

501

1.29

546

1.45

591

1.60

635

1.76

677

1.94

717

2.14

754

2.35

4800

463

1.17

509

1.36

554

1.53

599

1.68

642

1.85

684

2.03

723

2.24

760

2.46

5000

471

1.24

517

1.44

563

1.60

607

1.76

650

1.94

691

2.14

729

2.35

766

2.58

5200

479

1.32

525

1.52

571

1.69

615

1.85

657

2.04

698

2.24

736

2.47

772

2.70

5400

487

1.40

534

1.60

580

1.77

623

1.95

665

2.14

705

2.36

743

2.59

778

2.82

5600

496

1.48

544

1.69

589

1.87

632

2.05

674

2.25

713

2.48

749

2.72

785

2.95

5800

506

1.58

554

1.79

599

1.96

641

2.16

682

2.37

720

2.60

756

2.85

791

3.08

6000

516

1.68

564

1.89

608

2.07

650

2.27

691

2.49

728

2.73

763

2.98

798

3.22

6200

527

1.78

574

1.99

618

2.18

660

2.39

699

2.62

736

2.87

771

3.12

805

3.36

6400

538

1.89

585

2.09

628

2.29

669

2.51

708

2.75

743

3.01

778

3.26

812

3.50

6600

550

2.00

596

2.21

638

2.41

679

2.64

716

2.89

751

3.15

785

3.41

819

3.65

6800

562

2.12

607

2.33

649

2.54

688

2.78

725

3.04

759

3.30

793

3.56

826

3.79

7000

574

2.24

619

2.45

659

2.68

698

2.93

733

3.19

767

3.46

800

3.71

834

3.95

7200

587

2.36

630

2.59

670

2.83

707

3.08

742

3.34

775

3.61

808

3.87

841

4.10

7400

600

2.50

642

2.73

680

2.98

717

3.23

750

3.50

783

3.77

815

4.03

849

4.25

7600

612

2.64

653

2.88

691

3.13

726

3.40

759

3.67

791

3.94

823

4.19

856

4.41

7800

625

2.79

664

3.03

701

3.29

735

3.56

767

3.84

799

4.10

831

4.35

864

4.56

8000

638

2.94

676

3.20

711

3.46

744

3.73

776

4.01

807

4.27

839

4.51

872

4.72

8200

650

3.11

687

3.36

721

3.63

753

3.91

784

4.18

815

4.44

847

4.67

880

4.88

8400

662

3.27

698

3.54

731

3.81

762

4.08

793

4.36

823

4.61

855

4.84

888

5.04

8600

674

3.45

708

3.72

740

3.99

771

4.26

801

4.54

832

4.79

863

5.00

896

5.20

8800

685

3.63

719

3.90

750

4.17

780

4.45

809

4.72

840

4.96

871

5.17

904

5.36

9000

697

3.81

729

4.09

759

4.36

788

4.63

818

4.90

848

5.13

880

5.34

913

5.52

9200

708

4.00

739

4.28

768

4.55

797

4.82

826

5.08

857

5.30

888

5.50

921

5.69

9400

718

4.20

748

4.47

777

4.74

806

5.01

835

5.26

865

5.48

897

5.67

929

5.85

9600

729

4.39

758

4.67

786

4.94

814

5.20

843

5.44

874

5.65

905

5.84

938

6.01

Summary of Contents for TAA Series

Page 1: ...do not su persede or replace local or state codes WARNING Improper installation adjustment alteration service or maintenance can cause personal injury loss of life or damage to property Installation...

Page 2: ...2 3 16 x 25 x 2 SPECIFICATIONS General Data Model No TAA120S4D TAA150S4D TAA180S4D TAA240S4D Nominal Tonnage 10 12 5 15 20 Connections Liquid line o d in sweat 2 5 8 2 5 8 2 5 8 2 5 8 Suction Vapor li...

Page 3: ...GE PHASE 2HP 208 240V 3PH T2MSAV20LM1Y 92W63 x x 460V 3PH T2MSAV20LM1G 92W64 x x 575V 3PH T2MSAV20LM1J 92W65 x x 3HP 208 240V 3PH T2MSAV20LN1Y 92W66 x x x x 460V 3PH T2MSAV20LN1G 92W67 x x x x 575V 3P...

Page 4: ...V 3ph T3EH0050N 1G 46W71 x x 575V 3ph T3EH0050N 1J 46W75 x x ECONOMIZER T2ECON31L 1 44W94 x x T2ECON31M 1 44W95 x x T2ECON31N 1 44W96 x x Economizer Controls Differential Enthalpy Control 17W71 x x x...

Page 5: ...0 88 587 0 98 637 1 06 683 1 15 726 1 24 767 1 32 805 1 39 2700 486 0 81 542 0 92 596 1 02 646 1 11 692 1 2 734 1 29 775 1 37 812 1 45 2800 495 0 85 552 0 96 606 1 07 655 1 16 700 1 25 742 1 34 782 1...

Page 6: ...609 1 18 664 1 30 710 1 41 751 1 52 789 1 63 827 1 72 861 1 80 892 1 89 3300 624 1 24 677 1 36 722 1 48 761 1 59 799 1 70 836 1 79 870 1 88 901 1 97 3400 639 1 30 690 1 43 733 1 55 772 1 67 810 1 77 8...

Page 7: ...42 684 1 52 702 1 57 737 1 69 778 1 82 819 1 94 4400 600 1 37 635 1 45 672 1 56 691 1 62 717 1 72 756 1 86 796 1 98 836 2 09 4600 619 1 51 655 1 59 683 1 68 702 1 76 736 1 89 775 2 02 814 2 13 853 2...

Page 8: ...925 2 71 962 2 79 1000 2 88 5400 783 2 53 819 2 65 855 2 75 887 2 82 913 2 82 946 2 86 983 2 95 1021 3 03 5600 810 2 74 845 2 85 881 2 95 912 3 01 935 2 98 967 3 01 1004 3 10 1041 3 19 5800 835 2 95...

Page 9: ...3 12 6400 483 1 60 534 1 87 582 2 08 625 2 28 666 2 50 705 2 73 741 2 99 775 3 25 6600 491 1 70 544 1 97 591 2 18 633 2 39 674 2 62 712 2 86 747 3 12 781 3 38 6800 501 1 81 553 2 08 600 2 29 642 2 51...

Page 10: ...27 691 2 49 728 2 73 763 2 98 798 3 22 6200 527 1 78 574 1 99 618 2 18 660 2 39 699 2 62 736 2 87 771 3 12 805 3 36 6400 538 1 89 585 2 09 628 2 29 669 2 51 708 2 75 743 3 01 778 3 26 812 3 50 6600 55...

Page 11: ...890 4 06 929 4 25 969 4 45 1009 4 66 1049 4 86 1089 5 06 6800 861 4 00 898 4 20 936 4 40 976 4 60 1016 4 80 1056 5 00 1096 5 20 7000 868 4 15 905 4 35 943 4 54 983 4 74 1023 4 94 1063 5 14 1103 5 34 7...

Page 12: ...le horsepower are used be sure to keep within the service factor limitations outlined on the motor nameplate S Factory installed standard f Factory Installed with extended lead time BLOWER MOTOR ELECT...

Page 13: ...0 28 3400 0 17 0 23 0 06 0 08 0 10 0 06 0 30 3500 0 18 0 24 0 07 0 08 0 11 0 06 0 31 3600 0 18 0 25 0 07 0 08 0 12 0 06 0 32 TAA120 150 ACCESSORY AIR RESISTANCE ID AIR TAA120 Wet Coil Drop TAA150 Wet...

Page 14: ...08 0 11 0 33 5750 0 12 0 16 0 05 0 06 0 08 0 11 0 36 6000 0 13 0 18 0 05 0 07 0 10 0 12 0 38 6250 0 14 0 19 0 06 0 07 0 11 0 14 0 41 6500 0 15 0 20 0 06 0 07 0 11 0 14 0 43 6750 0 16 0 21 0 06 0 08 0...

Page 15: ...0 50 1 220 12 6 43 000 53 55 60 60 230 13 5 47 000 240 15 51 200 1 440 12 6 43 000 27 27 30 30 460 13 5 47 000 480 15 51 200 1 550 12 6 43 000 21 22 25 25 575 13 5 47 000 600 15 51 200 25 kW 3 2 208 1...

Page 16: ...1 200 550 12 6 43 000 1 575 13 5 47 000 22 23 25 25 600 15 51 200 25 kW 3 2 208 18 8 64 100 75 79 80 80 220 21 71 700 3 2 230 23 78 300 85 89 90 90 240 25 85 300 440 21 71 700 1 460 23 78 300 42 44 45...

Page 17: ...1 200 550 12 6 43 000 1 575 13 5 47 000 22 23 25 25 600 15 51 200 25 kW 3 2 208 18 8 64 100 75 79 80 80 220 21 71 700 3 2 230 23 78 300 85 89 90 90 240 25 85 300 440 21 71 700 1 460 23 78 300 42 44 45...

Page 18: ...200 550 12 6 43 000 1 575 13 5 47 000 23 26 25 30 600 15 51 200 25 kW 3 2 208 18 8 64 100 79 86 80 90 220 21 71 700 3 2 230 23 78 300 89 96 90 100 240 25 85 300 440 21 71 700 1 460 23 78 300 44 48 45...

Page 19: ...00 550 25 2 86 200 1 575 27 5 94 200 41 44 45 45 600 30 102 500 40 kW 2 208 29 3 100 000 115 123 125 125 220 32 8 112 000 2 230 35 8 122 300 131 139 150 150 240 39 133 200 440 32 8 112 000 1 460 35 9...

Page 20: ...500 550 25 2 86 100 1 575 27 6 94 200 44 48 45 50 600 30 102 500 40 kW 2 208 29 3 100 000 123 132 125 150 220 32 8 112 000 2 230 35 8 122 300 139 148 150 150 240 39 133 200 440 32 8 112 000 1 460 35...

Page 21: ...de energize all 24 volt circuits E Terminal Block TB1 All field wring connections are made at terminal block TB1 F Condensate Pan and Over Flow Relay K220 Switch S149 A reversible drain pan is provide...

Page 22: ...blower performance tables Measure the indoor blower motor s rpm Measure the static pressure external to the unit NOTE The indoor coil must be dry and the air filters must be in place when the followi...

Page 23: ...nd the contacts open The relay energizes different stages of heat 4 Relays K9 and K19 Relays K9 and K19 are used to electrically isolate the TAA 24 volts components from the T3EHA 24 volt components T...

Page 24: ...age 24 V Wiring Diagrams TAA072 240 SEQUENCE OF OPERATION 1 W1 heat demand energizes the economizer relay K43 2 When K43 1 closes blower relay K3 is energized 3 K3 1 closes energizing indoor blower B3...

Page 25: ...and energizes the econo mizer relay K43 and heat relay K9 K43 1 closes ener gizing blower relay K3 2 K3 1 closes energizing indoor blower B3 K9 1 closes energizing contactor K15 3 K15 1 closes and ass...

Page 26: ...19 is energized Unit is ready for se cond stage heat but ONLY if there is a W2 call 3 K15 1 closes and assuming primary limit S15 and secon dary limit S20 are closed heating elements HE1 and HE2 are e...

Page 27: ...emand energizes the econo mizer relay K43 and heat relay K9 K43 1 closes ener gizing blower relay K3 2 K3 1 closes energizing indoor blower B3 K9 1 closes energizing contactor K15 3 K15 1 closes and a...