TSA*H4 SERIES

Evacuating Line Set and Indoor Coil 

A

Open both manifold valves and start the vacuum pump.

B

Evacuate the line set and indoor unit to an 

absolute pressure

 of 23,000 microns (29.01 inches of mercury).

NOTE 

— During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure

indicates a relatively large leak. If this occurs, 

repeat the leak testing procedure

.

NOTE 

— The term 

absolute pressure

 means the total actual pressure within a given volume or system, above the absolute zero of

pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

C

When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:

Close manifold gauge valves

Close valve on vacuum pump

Turn off vacuum pump

Disconnect manifold gauge center port hose from vacuum pump

Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.

Open manifold gauge valves to break the vacuum in the line set and indoor unit.

Close manifold gauge valves.

D

Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the

dry nitrogen from the line set and indoor unit.

E

Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the

absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

F

When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an

upright cylinder of HFC-410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and
indoor unit.

G

Perform the following:

OUTDOOR

UNIT

TO VAPOR

SERVICE VALVE

TO LIQUID LINE
SERVICE VALVE

MICRON

GAUGE

VACUUM PUMP

A34000 1/4 SAE TEE WITH
SWIVEL COUPLER

500

MANIFOLD

GAUGE SET

HFC-410A

RECOMMEND

MINIMUM 3/8" HOSE

A

Connect low side of manifold gauge set
with 1/4 SAE in-line tee to 

vapor 

line

service valve

B

Connect high side of manifold gauge
set to 

liquid 

line service valve

C

Connect micron gauge available
connector on the 1/4 SAE in-line tee.

D

Connect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port
line will be used later for both the
HFC-410A and nitrogen containers.

HIGH

LOW

1

2

3

4

5

6

7

8

9

10

11 12

1/6 TURN

NITROGEN

1

CONNECT GAUGE SET

A

B

C

D

2

EVACUATE THE SYSTEM

NOTE 

— Remove cores from service valves (if not already done).

Close manifold gauge valves.

Shut off HFC-410A cylinder.

Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.

Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.

Figure 13. Evacuating System

Summary of Contents for T-Class TSA H4 Series

Page 1: ...service valve s internal seals INSTALLATION INSTRUCTIONS T Classt TSA H4 Units AIR CONDITIONER 507994 01 7 19 TABLE OF CONTENTS Shipping and Packing List 1 General 1 Unit Dimensions 2 Typical Unit Parts Arrangement 2 Model Number Identification 3 Operating Manifold Gauge Set and Service Valves 3 Recovering Refrigerant from Existing System 5 New Unit Placement 6 New or Replacement Line Set 7 Brazin...

Page 2: ...SA060H4N4 32 1 4 819 33 1 4 845 Typical Unit Parts Arrangement COMPRESSOR HARNESS CONNECTION LIQUID LINE SERVICE VALVE SUCTION LINE SERVICE VALVE DISCHARGE LINE HIGH PRESSURE SWITCH S4 COMPRESS0R B1 GROUND LUG CONTACTOR K1 CONTROL CAPACITOR C12 MOUNTING LOCATION VARIES CONTROL WIRE LOOP CUTOUT FOR HIGH VOLTAGE CONDUIT NOTE Plumbing layout and compressor type may vary between model sizes CRANKCASE ...

Page 3: ...ell Harness Scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrigerant loss during shipping and handling Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench or stripping the valve stem recess See the Lennox Service and Application Not...

Page 4: ...opriately sized wrench 2 Use an appropriately sized wrenched to open To open valve rotate stem counterclockwise 90 To close rotate stem clockwise 90 1 2 3 4 5 6 7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench 2 Connect gauge set to se...

Page 5: ...ction that is designed to unload the scrolls compressor stops pumping when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips drive bearings and internal seals...

Page 6: ... away from windows Two 90 elbows installed in line set will reduce line set vibration Figure 5 Placement and Slab Mounting New Unit Placement See Unit Dimensions on page 2 for sizing mounting slab platforms or supports Refer to figure 4 for mandatory installation clearance requirements CAUTION In order to avoid injury take proper precaution when lifting heavy objects POSITIONING CONSIDERATIONS Con...

Page 7: ...lbows and if there is a rise or drop of the piping If refrigerant lines are routed through a wall seal and isolate the opening so vibration is not transmitted to the building Pay close attention to line set isolation during installation of any HVAC system When properly isolated from building structures walls ceilings floors the refrigerant lines will not create unnecessary vibration and subsequent...

Page 8: ... material or anchored heavy nylon wire ties 8 FEET 2 43 METERS STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION ...

Page 9: ...ystem may result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system use a regulator that can control the pressure down to 1 or 2 psig 6 9 to 13 8 kPa CAUTION Brazing alloys and flux contain materials which are hazardous to your healt...

Page 10: ...E AWAY FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND DEBUR CAP AND CORE REMOVAL Cut ends of the refrigerant lines square free from nicks or dents and debur the ends The pipe must remain round Do not crimp end of the line Remove service cap an...

Page 11: ...ICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set The braze when complete must be quenched with water to absorb any residual heat 2 Do not open service valves until refrigera...

Page 12: ... on the recovery machine with an empty recovery tank to the gauge set D Connect recovery tank to recovery machines per machine instructions CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE A B C D B OR A Set the recovery machine for liquid recovery and start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor u...

Page 13: ...DISTRIBUTOR ASSEMBLY A Remove the field provided fitting that temporary reconnected the liquid line to the indoor unit s distributor assembly B Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil C Attach the stubbed end of the expansion valve to the liquid line...

Page 14: ...R UNIT HIGH LOW NITROGEN A With both manifold valves closed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the line set and indoor unit Weigh in a trace amount of HFC 410A A trace amount is a maximum of two ounces 57 g refrigerant or thr...

Page 15: ... and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC 410A refrigerant Open the manifold gauge valve...

Page 16: ...st conform with current local codes and the current Canadian Electrical Code CEC Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air handler for low voltage control power 24VAC 40...

Page 17: ... voltage control wire strain relief and to maintain separation of field installed low and high voltage circuits NOTE For proper voltages select thermostat wire control wires gauge per table above NOTE Do not bundle any excess 24VAC control wires inside control panel A Run 24VAC control wires through hole with grommet and secure with provided wire tie B Make 24VAC thermostat wire connections Locate...

Page 18: ...tion line service valve stems Operating Service Valves on page 3 to release the refrigerant charge contained in outdoor unit into the system 4 Replace the valve stem caps and tighten as specified in Operating Service Valves on page 3 5 Check voltage supply at the disconnect switch The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have c...

Page 19: ... LIQUID PHASE CONNECTIONS FOR TESTING AND CHARGING GAUGE SET A C D LOW HIGH B SUCTION LINE SERVICE PORT CONNECTION Figure 16 Manifold Gauge Set Setup and Connections WHEN TO CHARGE Warm weather best Can charge in colder weather CHARGE METHOD Determine by Metering device type Outdoor ambient temperature REQUIREMENTS Sufficient heat load in structure Indoor temperature between 70 80ºF 21 26ºC Manifo...

Page 20: ...T Chart START Measure outdoor ambient temperature 64ºF 17 7ºC and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with table 3 or 6 3 Conduct leak check evacuate as previously outlined 4 Weigh in the unit nameplate charge plus any charge required for line set differences over feet Liquid Line Set Diameter g per 1 5 m adjust from 4 6 m line set 9 5 mm 85 g per 1 5 m NOTE If...

Page 21: ...e to determinesaturation temperature see table 4 SATº ______ 10 Subtract to determine subcooling SCº SATº_____ LIQº _____ SCº _____ 11 Compare results with table below Figure 21 HFC 410A Subcooling TXV Charge MORE or LESS If value is LESS than shown add refrigerant If refrigerant is added or removed verify charge using the Approach Method 64ºF and BELOW 65ºF and ABOVE ABOVE or BELOW ºF ºC 036 048 ...

Page 22: ... thermostat switch S40 located on the liquid line see figure 1 for location When liquid line temperature drops below 50 F the thermostat closes energizing HR1 The thermostat will open de energizing HR1 once liquid line temperature reaches 70 F HIGH PRESSURE SWITCH S4 TSA H4 units are equipped with a high pressure switch that is located in the liquid line of the compressor The switch SPST manual re...

Page 23: ...they could cause prolonged exposure to the outdoor unit by treated water Prolonged exposure of the unit to treated water i e sprinkler systems soakers waste water etc will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit Outdoor Coil The outdoor unit must be properly maintained to ensure its proper operation Please contact your dealer to schedule p...

Page 24: ...s usually unnecessary to fully remove the inner mesh screen 4 Drape the mesh screen back and wash the coil When all the debris has been removed from the coil reinstall the mesh screen by positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins 5 If the push pin is loose and tends not to stay in place brush the fins...

Reviews: