background image

Summary of Contents for T-CLASS TS Series

Page 1: ...gn Sequence A 1st Generation B 2nd Generation Brand Family T T Class Product Line Unit Type S Split System Air Conditioner Nominal Cooling Capacity Tons 072 6 Tons 090 7 5 Tons 120 10 Tons 150 12 5 To...

Page 2: ...e years in non residential applications All other covered components one year in non residential applications Refer to Lennox Equipment Limited Warranty certificate for specific details Approvals All...

Page 3: ...ing pressure Manual reset Loss of Charge Switch Shuts off unit if liquid line pressure falls below setting Provides loss of charge and freeze up protection Automatic reset Hi Capacity Drier s Drier tr...

Page 4: ...base pan is provided with this option Field Installed Coil Guards Heavy duty sheet metal and metal mesh enclosures protect coils from damage Field installed Hail Guards Heavy duty sheet metal and met...

Page 5: ...ccessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1 C0S...

Page 6: ...075 Watts 430 580 ELECTRICAL DATA Line voltage data 60 hz 3 phase 208 230V 460V 575V 208 230V 460V 575V 2 Maximum Overcurrent Protection amps 45 20 15 50 25 20 3 Minimum circuit ampacity 27 14 11 35 1...

Page 7: ...60 hz 3 phase 208 230V 460V 575V 208 230V 460V 575V 2 Maximum Overcurrent Protection amps 70 40 25 50 25 20 3 Minimum circuit ampacity 43 24 18 41 21 15 Compressor No of Compressors 1 1 1 2 2 2 Rated...

Page 8: ...575V 208 230V 460V 575V 208 230V 460V 575V 2 Maximum Overcurrent Protection amps 60 30 25 90 40 30 100 50 40 3 Minimum circuit ampacity 49 25 20 66 33 25 78 43 32 Compressor No of Compressors 2 2 2 2...

Page 9: ...roller C0CTRL07AE1L 17M10 x x x x x x x NOTE The catalog and model numbers that appear here are for ordering field installed accessories only f Factory Installed with extended lead time X Field Instal...

Page 10: ...9 2 2 CX34 62D 6F Factory TXV Down Flow Indoor Coils 111 400 107 000 10 6 2 2 CR33 50 60C 2F 1 91M02 Horizontal Indoor Coils 116 000 111 000 10 8 2 2 CH33 62D 2F 1 91M02 2 TSA120S4S 2 10 TON Air Handl...

Page 11: ...clude indoor blower motor heat deduction Units with capacity of 65 000 Btuh or greater are certified in accordance with the ULE certification program which is based on ARI Standard 340 360 95_F outdoo...

Page 12: ...ain tained on one of the sides adjacent to the control box Clearance to one of the other three sides must be 36 in 914 mm Clearance to one of the remaining two sides may be 12 in 305 mm and the final...

Page 13: ...4 1149 REFRIGERANT LINE CONNECTIONS SEE DETAIL REFRIGERANT LINE CONNECTIONS DETAIL EE FF CONTROL BOX ACCESS COMPRESSOR COMPRESSOR CENTER OF GRAVITY INLET AIR INLET AIR DISCHARGE AIR BASE LIFTING HOLE...

Page 14: ...60 1 8 1527 57 7 8 1470 COMPRESSOR BASE FRONT VIEW FORKLIFT SLOTS Both Sides CONTROL BOX ACCESS ELECTRICAL INLETS Above Refrigerant Lines TOP VIEW FF EE INLET AIR INLET AIR AA BB CC DD CENTER OF GRAVI...

Page 15: ...OP VIEW FORKLIFT SLOTS Both Sides SIDE VIEW 88 3 4 2254 48 3 4 1238 3 1 2 89 45 1 4 1149 FF EE CENTER OF GRAVITY AA BB CC DD 3 3 4 95 6 1 2 165 BASE COMPRESSOR SUCTION LINE 2 LIQUID LINE 2 OUTDOOR FAN...

Page 16: ..._F 29_C kBtuh kW 75_F 24_C 80_F 27_C 85_F 29_C 63_F 17_C 1920 905 69 2 20 3 4 84 68 82 97 66 0 19 3 5 37 69 85 99 62 5 18 3 5 97 70 87 1 00 58 7 17 2 6 65 72 91 1 00 2400 1135 72 5 21 2 4 85 72 90 1 0...

Page 17: ...kBtuh kW 75_F 24_C 80_F 27_C 85_F 29_C 63_F 17_C 1920 905 72 1 21 1 4 86 67 82 97 68 9 20 2 5 39 68 84 1 00 65 3 19 1 5 99 70 87 1 00 61 3 18 0 6 68 72 91 1 00 2400 1135 76 0 22 3 4 88 71 89 1 00 72 4...

Page 18: ...8 29 2 6 71 43 57 70 94 8 27 8 7 42 43 58 72 89 1 26 1 8 24 43 59 74 3600 1700 107 6 31 5 6 15 44 59 73 102 3 30 0 6 77 44 59 76 97 4 28 5 7 48 45 62 79 91 5 26 8 8 29 46 63 82 COOLING CAPACITY 2 TSA...

Page 19: ...C 85_F 29_C kBtuh kW 75_F 24_C 80_F 27_C 85_F 29_C 63_F 17_C 2400 1135 86 1 25 2 5 73 68 81 96 82 2 24 1 6 36 69 83 98 78 3 22 9 7 08 70 86 1 00 73 8 21 6 7 91 72 89 1 00 3000 1415 89 9 26 3 5 80 72 8...

Page 20: ...6 04 43 56 69 134 1 39 3 6 67 44 57 70 129 1 37 8 7 38 44 58 72 123 1 36 1 8 18 44 59 74 9600 4530 143 4 42 0 6 12 45 60 74 137 9 40 4 6 75 45 60 75 132 3 38 8 7 45 45 61 78 126 7 37 1 8 25 45 63 80...

Page 21: ...24 6 36 5 7 30 44 58 71 119 5 35 0 8 10 45 59 72 113 7 33 3 9 01 45 60 74 107 3 31 4 10 04 45 62 77 4800 2265 128 5 37 7 7 37 45 61 75 122 9 36 0 8 17 46 62 77 116 8 34 2 9 07 46 63 80 110 2 32 3 10 1...

Page 22: ...00 1890 132 4 38 8 7 22 41 54 67 126 5 37 1 8 15 41 56 69 119 4 35 0 9 22 42 57 71 112 1 32 9 10 45 43 58 75 4800 2265 136 5 40 0 7 29 42 58 73 129 9 38 1 8 21 43 59 75 122 7 36 0 9 27 43 60 78 115 1...

Page 23: ...90 129 5 38 0 7 17 41 53 66 123 4 36 2 8 10 42 54 67 117 2 34 3 9 19 42 56 68 110 1 32 3 10 43 43 57 71 4800 2265 133 8 39 2 7 24 42 56 69 127 4 37 3 8 17 43 57 72 120 5 35 3 9 24 43 59 75 113 0 33 1...

Page 24: ...0 69 3 20 3 2 81 41 52 62 66 7 19 5 3 17 41 52 63 64 0 18 8 3 58 41 53 65 60 9 17 8 4 04 42 54 66 4800 2265 71 8 21 0 2 84 42 54 66 69 1 20 3 3 20 42 54 67 66 1 19 4 3 61 42 55 68 63 0 18 5 4 07 43 56...

Page 25: ...46 4 9 05 42 54 65 151 2 44 3 10 07 42 54 66 143 6 42 1 11 21 42 56 68 135 0 39 6 12 53 43 57 70 4800 2265 163 8 48 0 9 06 43 56 70 156 3 45 8 10 07 43 57 71 148 5 43 5 11 23 43 58 74 139 8 41 0 12 5...

Page 26: ...2 55 67 85 0 24 9 4 08 43 56 69 81 7 23 9 4 54 43 57 70 78 0 22 9 5 03 43 58 72 6000 2830 91 0 26 7 3 69 43 58 72 87 7 25 7 4 09 43 59 73 84 3 24 7 4 54 44 60 75 80 5 23 6 5 05 45 61 77 COOLING CAPACI...

Page 27: ...7 16 07 45 59 72 6000 2830 201 5 59 1 11 81 45 59 72 192 5 56 4 13 06 45 60 74 183 1 53 7 14 51 46 61 75 173 0 50 7 16 17 47 62 78 7200 3400 207 6 60 8 11 92 46 62 77 198 5 58 2 13 17 47 63 79 188 6 5...

Page 28: ...3775 269 4 79 0 15 38 46 60 74 258 0 75 6 17 12 46 62 76 244 8 71 7 19 10 46 63 78 231 0 67 7 21 37 47 65 80 9600 4530 277 1 81 2 15 51 46 63 80 264 8 77 6 17 23 47 65 81 251 1 73 6 19 20 47 66 84 236...

Page 29: ...the edition date of standards This article does not require compliance with standard but is merely a listing of references used Article below should list only those industry standards referenced in th...

Page 30: ...e Include names and addresses of spare part suppliers 3 Provide brief description of unit with details of function operation control and component service 4 Commissioning Report Submit commissioning r...

Page 31: ...teel b Pre painted finish c Refrigerant line connections to be located outside the unit d Control access e All controls factory wired 2 Compressor a Scroll Type b Resiliently mounted on rubber mounts...

Page 32: ...written data including product technical bulletins product catalog installation instructions and product carton installation instructions 3 02 EXAMINATION A Site Verification of Conditions Verify sub...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installation and servic...

Reviews: