background image

Do you want to lock the keypad? 

 

Reminder clean filter!

 

Alarm!

 

Commissioning

 (by qualified HVAC installer) 

To adapt the controller to your system and optimize the control performance, a number of 
control parameters can be adjusted. This can also be made during operation without 
opening the controller. 

Control sequence 

Recalibrating the sensor 

Energy saving mode 

 

 

If you want to change the factory-set temperature setpoints (15 °C for heating 
and 30 °C for cooling), the parameter P11 and P12 need to be adjusted. 

Important: 

The setpoint of energy saving mode can be set to 

OFF

; this 

means that the controller is then not active! 

Risk of frost, 

i.e. no protective 

heating or cooling function. 

Control parameter 

If you want to change the control parameters, proceed as follows:

  

 

+ / - 

 

+ / - 

+ / - 

 

+ / - 

1.  Set the controller to standby   

 

2. Press 

-

 and 

+

 simultaneously for a minimum of 3 seconds.  

Release them and, within 2 seconds, press the 

+

 again for 3 seconds. The display will show “P01”. 

3.  Select the required parameter by repeatedly pressing the 

+

 or 

 button. 

4. Press 

+

 and 

 simultaneously, the current value of the selected parameter starts to flash, which can be 

changed by repeatedly pressing 

+

 or 

-

5. By pressing 

+

 and 

-

 simultaneously again the next parameter will be displayed. 

6.  If you wish to display and change additional parameters, repeat steps 3 through 5. 

7.  10 seconds after the last display or setting, all changes are stored and the controller will leave parameter enter 

mode. 

   Please record all changes you make!  

(all temperature settings can be made in increments of 0.5 K) 

 

 

 

If the keypad lock function is enabled by parameter P14, then pressing 7 
seconds on the operating mode button  , the keypad will be locked or 
unlocked respectively.  
If “Auto lock” is configured, then the controller will automatically lock the 
keypad after 30 seconds of the last adjustment. 

    

FIL 

This message reminds you to clean the filter on your HVAC equipment. 
It will appear after  …………….….. “fan operating hours” and disappear 
when the controller is set to standby ( ). 

This reminder must be configured 

by your HVAC installer.

 

    

AL1 

    

AL2 

This alarm message tells you an external alarm has occurred: 

    

AL1 :

……………………………..….  

    

AL2 :

…………………………………. 

The alarms are configured by your HVAC installer

 

 

The controller can be used in systems either for 

heating only

 or 

cooling only

manually selection of heating or cooling

, or 

automatic heating / cooling 

changeover

. Depending on the selected application, the relevant modes are 

available and can be adjusted by commissioning parameter P01 if needed.  
The factory setting for 2-pipe and single duct application is “C

ooling only”

and for 4 pipe application “Heating and Cooling” 

 

If the room temperature displayed by the controller does not agree with the 
temperature effectively measured, the temperature sensor can be 
recalibrated. With parameter P05 the temperature can be adjusted by + or – 
0.5 °C up to a maximum of + / - 3 °C. 

Para-
meter

Controller’s parameter factory settings: 

 

Setting range  

RDF3… 
RDU340. 

P01 Control 

sequence 

 

2-pipe

…: [0…3] 

1 (Cool only) 

 

4-pipe:.   

 [2…4] 

4 (Heat&Cool) 

0:= Heating only 

1:= Cooling only 

2:= Manual H or C 

3:= Auto Changeover 

4:= Heating & cooling 

 

P02  Mode selection by user operating mode button 

1 (Stb, Comf) 

1 = Stb, Comf 

2 = Stb, Comf, Eco 

 

P04  Selection of °C or °F 

°C 

°C or °F 

 

P05 Sensor 

calibration 

0.0 K 

– 3 ... +3 K 

 

P06  Standard temperature display 

0 (Room temp.) 

0:= Room temp 

1:= Setpoint 

 

P07  Additional user info 

0 (no display) 

0:= no display 

1:= Temp in °C + °F 

 

P08  Comfort basic setpoint 

21 °C 

5 ... 40 °C 

 

P09  Minimum setpoint limitation in Comfort 

(Wmin

Comf

)  5 °C 

5 ... 40 °C 

 

P10  Maximum setpoint limitation in Comfort 

(Wmax

Comf

) 35 °C 

5 ... 40 °C 

 

P11  Setpoint of heating in Energy Saving  

(Wheat

Eco

)  15 °C 

OFF, 5 °C…Wcool

Eco

 

 

P12  Setpoint of cooling in Energy Saving 

30 °C 

OFF, Wheat

Eco

…40°C  

P13  Electrical heater in cooling mode 

ON 

OFF:= disabled  

ON:=   enabled 

 

P14 Keypad 

lock 

(Pressing 7 seconds on the operating mode button  , the 

keypad will be locked or unlocked respectively) 

0 (Disabled) 

0:= Disabled 

1:= Auto lock 

2:= Manual lock 

 

P01

P02

P08

P13

+

-

+

-

-

+

3057z03

P14

-

+

-

P12

+

-

Summary of Contents for RDF300.02 ARG71

Page 1: ...lennoxemeia com RDF300 02 ARG71 Installation operating and maintenance RDF300 02 Remote control ARG71 Installation plastic box RDF300 02 IOM 0509 E ...

Page 2: ......

Page 3: ...Mounting Location of Thermostat Preparation and Deliverables Semi Flush Mounting RDF300 RDF340 RDF400 5 ...

Page 4: ...I III N1 B2 S1 M1 QAH11 1 ARG86 3 E1 5 2 A max 5 2 A max 5 2 A max AC 230 V C1 ON 1 2 4 pipe en L N 10 A L N Q1 Q2 Q3 Y11 Y21 AC 230 V X1 M X2 I II III N1 M1 Y1 Y2 5 2 A max 5 2 A max 5 2 A max B2 S2 B1 S1 G G0 G G0 Q1 Q2 Q3 Y10 Y20 AC 24V X1 M X2 I II III N1 M1 L N L Y1 Y2 max 1 mA max 1 mA S1 QAH11 1 QAA32 G G0 AC 24 V L N AC 230 V L N 10 A L N Q1 Q2 Q3 Y11 Y21 AC 230 V X1 M X2 I II III N1 S1 M1...

Page 5: ...stall 1 connexion 2 assembly and screwing 3 fitting together of regulation and displaying element without any risk of supplying cable handing Important Please check that controller fits to the case delivered Controller dimensions 53 mm L x 68 mm H x 46 mm P request adapted case with a 60 3 mm fixing distance 1 2 3 ...

Page 6: ...ut rating Heating cooling DC 0 10 V Electric reheater relay DC 0 10 V max 1 mA Max 5 2 A AC 230 V Input Multifunctional X1 X2 NTC cable sensor like QAH11 switch Setpoint setting range 5 40 C in 0 5 C increments Control algorithm 2P PI P Environmental conditions Temperature Relative humidity 0 50 C 95 Mounting type Semi flush mount fixing centers 60 3 mm Dimension visible part 86mm x 86mm x 14 mm M...

Page 7: ...F semi flush mounted room temperature controllers Main features Size 75 mm x 75 mm x 51 mm with fixing centers 60 3 mm For installation of all semi flush mount room temperature controllers Conformant to BSI standard BS4662 EN 50086 2 1 IEC 670 ...

Page 8: ...rates independently and always runs at the same speed Low medium or high Low fan speed Medium fan speed High fan speed By a single speed fan the mode can be changed between and Do you want to set your controller to standby Press the operating mode button several times until the display shows the symbol to indicate that standby is selected In standby only frost protection is active factory setting ...

Page 9: ...e filter on your HVAC equipment It will appear after fan operating hours and disappear when the controller is set to standby This reminder must be configured by your HVAC installer AL1 AL2 This alarm message tells you an external alarm has occurred AL1 AL2 The alarms are configured by your HVAC installer The controller can be used in systems either for heating only or cooling only manually selecti...

Page 10: ......

Page 11: ......

Page 12: ...BELGIUM AND LUXEMBOURG FRANCE GERMANY ITALY NETHERLANDS POLAND PORTUGAL SALES OFFICES OTHER COUNTRIES Due to Lennox s ongoing commitment to quality the specifications ratings and dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installation and service must...

Reviews: