background image

Page 32

 7. If intake and exhaust piping must be run up a side wall

to position above snow accumulation or other ob­
structions, piping must be supported. At least one
bracket must be used within 6” from the top of the el­
bow and then every 24” (610mm) as shown in figure
41, to prevent any movement in any direction. When
exhaust and intake piping must be run up an outside
wall, the exhaust piping must be terminated with pipe
sized per table 17.The intake piping may be equipped
with a 90° elbow turndown. Using turndown will add 5
feet (1.5m) to the equivalent length of the pipe.

 8. A multiple furnace installation may use a group of up to

four terminations assembled together horizontally, as
shown in figure 38.

FIGURE 36

DIRECT VENT CONCENTRIC ROOFTOP TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

Minimum

Above Average

Snow

Accumulation

SHEET METAL STRAP

(Clamp and sheet metal strap

must be field installed to support
the weight of the termination kit.)

FLASHING

(Not Furnished)

CLAMP

FIELD-PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

1 1/2” (38mm) accelerator

provided on 71M80 & 44W92

kits for ML193UH045P24B,

070P24B & 070P36B

12” (305mm)

INTAKE

AIR

EXHAUST

VENT

12” (305mm) Min.

above grade or

average snow
accumulation.

FIGURE 37

DIRECT VENT CONCENTRIC WALL TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

INTAKE

AIR

INTAKE

AIR

INTAKE

AIR

OUTSIDE

WALL

GRADE

CLAMP

(Not Furnished)

FIELD-PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

EXHAUST

VENT

1-1/2” (38mm) accelerator

provided on 71M80 & 44W92

kits for ML193UH045P24B,

070P24B & 070P36B

EXHAUST

VENT

FIGURE 38

EXHAUST

VENT

INTAKE

AIR

5-1/2”

(140mm)

Front View

12”

(305mm)

5”

(127mm)

18” MAX.

(457mm)

EXHAUST VENT

INTAKE

AIR

OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT

INSTALLATION OF DIRECT VENT WALL TERMINATION KIT

(30G28 or 81J20)

Inches (mm)

Side View

12” (305mm) Min.

above grade or

average snow 

accumulation.

optional intake elbow

FIGURE 39

2” EXTENSION FOR 2”  PVC
PIPE1” EXTENSION FOR 3”
PVC PIPE

1-1/2” ACCELERATOR

(

all -45, -070 and -090 units)

FURNACE

EXHAUST

PIPE

FURNACE

INTAKE

PIPE

4''

GLUE EXHAUST

END FLUSH INTO

TERMINATION

FLAT
SIDE

FLUSH-MOUNT SIDE WALL TERMINATION

51W11 (US) or 51W12 (Canada)

ML193UH DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

FIGURE 40

3” - 8”

(76mm-

203mm)

STRAIGHT-CUT OR

ANGLE-CUT IN DIRECTION

OF ROOF SLOPE *

EXHAUST VENT

1/2” (13mm) 

WEATHERPROOF

INSULATION

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

ALTERNATE

INTAKE PIPE

INTAKE PIPE

INSULATION (optional)

EXTERIOR

PORTION OF

CHIMNEY

INSULATE

TO FORM

SEAL

SHEET

METAL TOP

PLATE

*SIZE TERMINATION
PIPE PER TABLE 17.

Minimum 12” (305MM)

above chimney top

plate or average snow

accumulation

8” - 12”

(203mm - 305mm)

3”-8”

(76mm-203mm)

NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver­
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus­
trated. In any exterior portion of chimney, the exhaust vent must be insulated.

Summary of Contents for ML193UH045P36B

Page 1: ...ailed description on how this is done All specifications are subject to change Procedures out lined in this manual are presented as a recommendation only and do not supersede or replace local or state...

Page 2: ...according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces SPECIFICATIONS Gas Heating Performance Model No ML193UH090P48C ML193UH110P48C ML193UH110P60C ML193...

Page 3: ...2 in 44W92 44W92 3 in 44W93 44W93 Flush Mount 2 2 1 2 or 3 in 51W11 51W11 51W11 Wall Close Couple US 2 in 22G44 3 in 44J40 44J40 44J40 Wall Close Couple WTK Canada 2 in 30G28 3 in 81J20 81J20 81J20 T...

Page 4: ...1225 480 1030 405 0 80 1415 615 1265 510 1125 445 980 385 0 90 1270 565 1165 470 1060 420 900 350 ML193UH110P48C PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts at Various Blo...

Page 5: ...80 1660 855 1505 710 1290 585 0 90 1735 1135 1620 830 1450 685 1270 575 1665 1130 1520 810 1415 675 1210 560 ML193UH135P60D PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts at...

Page 6: ...ASSEMBLY CONTROL BOX includes integrated control transformer and interlock switch COMBUSTION AIR INDUCER BLOWER ACCESS DOOR BURNER ACCESS PANEL COMBUSTION AIR PRESSURE SWITCH PRIMARY LIMIT GAS VALVE...

Page 7: ...gnition control system consists of an integrated con trol figure 4 ignitor figure 10 and flame sensor figure 10 The integrated control and ignitor work in combination to ensure furnace ignition and ig...

Page 8: ...line voltage conditions Fan Control The fan on time of 30 seconds is not adjustable The fan off delay amount of time that the blower operates after the heat demand has been satisfied may be adjusted...

Page 9: ...lame 5 times during single heating demand SLOW FLASH OFF Flame sensed without gas valve energized ON SLOW FLASH Rollout switch open OR 12 pin connector improperly attached ON ON OFF ON OFF ON Circuit...

Page 10: ...ds of trial for ignition If ignition is not proved during the trial for ignition the integrated control will try four more times with an inter purge and warm up time between trials of 30 seconds After...

Page 11: ...g Speed 120VAC Blower Heating Speed 120VAC Dead terminals to park alternate spd taps Continuous blower Neutral terminals 120VAC PUSH BUTTON LED TWIN TWIN Twinning Terminal 24VAC DEMAND CAI GAS VALVE 1...

Page 12: ...NO JUMPER FIGURE 8 60 90 120 180 60 90 120 180 60 90 120 180 60 90 120 180 60 Second off Time 90 Second off Time 120 Second off Time 180 Second off Time Twinning 2 ML193UH Furnaces Integrated control...

Page 13: ...TWO STAGE THERMOSTAT Call For Cool Call For Fan Call For 1st Stage Heat Call For 2nd StageHeat R Y G W1 W2 Y W C Y W R R G C G TWIN TWIN TWIN 2 TWIN 1 ISOLATION RELAY Call For Cool Call For Fan Call F...

Page 14: ...sor can be removed for service with out removing any part of the burners During operation flame is sensed by current passed through the flame and sensing electrode The ignition control allows the gas...

Page 15: ...then the problem is with the wiring between the jack plug and the control If reading is not correct the issue is the ignitor Test 3 Check ignitor for correct voltage Insert meter probes into terminals...

Page 16: ...secondary heat exchangers and exhausted out the exhaust vent pipe 6 Burners Figure 13 All units use inshot burners Burners are factory set and do not require adjustment Burners can be removed as an a...

Page 17: ...header box The switch monitors across the combustion air inducer orifice to insure proper flow through the heat exchanger The switch is a SPST N O prove switch electrically con nected to the integrat...

Page 18: ...be the pressure differential The pressure differential should be greater than those listed in table 10 5 Remove thermostat demand and allow to cycle off 6 Remove manometer and tee s Reinstall combus t...

Page 19: ...TM SPECIFICATION PVC CPVC Primer F656 PVC Solvent Cement D2564 CPVC Solvent Cement F493 ABS Solvent Cement D2235 PVC CPVC ABS All Purpose Cement For Fittings Pipe of the same material D2564 D2235 F493...

Page 20: ...in take pipe to the connector if desired Use a drill or self tap ping screw to make a pilot hole DANGER DANGER OF EXPLOSION Fumes from PVC glue may ignite during system check Allow fumes to dissipate...

Page 21: ...ML193UH furnace replaces a furnace which was commonly vented with another gas appliance the size of the existing vent pipe for that gas ap pliance must be checked Without the heat of the original furn...

Page 22: ...pe in these applications NOTE The exhaust collar on all models is sized to accom modate 2 Schedule 40 vent pipe In horizontal applica tions any transition to exhaust pipe larger than 2 must be made in...

Page 23: ...090 110 135 045 070 090 110 135 045 070 090 110 135 1 73 58 42 22 n a 105 90 64 39 n a 121 121 114 114 105 2 68 53 37 17 100 85 59 34 116 116 109 109 100 3 63 48 32 12 95 80 54 29 111 111 104 104 95 4...

Page 24: ...gth of 2 PVC pipe possible NOTE Exhaust pipe and intake pipe must be the same diameter or FIGURE 23 TRANSITION SIDE VIEW 2 2 2 2 or TYPICAL EXHAUST PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON DIRECT...

Page 25: ...use the shortest length of 2 PVC pipe possible NOTE Intake and exhaust pipe must be the same diameter or FIGURE 25 TYPICAL AIR INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT VENT APPLICATIONS RIGHT HAN...

Page 26: ...ZONTAL NON DIRECT VENT APPLICATIONS Horizontal Right Hand Air Discharge Application Shown INTAKE DEBRIS SCREEN Provided OR NOTE Debris screen may be positioned straight out preferred or with an elbow...

Page 27: ...ons combustion air is taken from outdoors and the flue gases are discharged to the out doors The ML193UH is then classified as a direct vent Category IV gas furnace In both Non Direct Vent and Direct...

Page 28: ...32 28 40 35 0 to 20 18 to 29 2 in 10 9 20 18 30 28 24 24 N A N A 2 1 2 in 8 N A 14 N A 20 N A 32 N A N A N A 3 in 4 3 10 8 16 14 26 23 30 26 1Refer to 99 Minimum Design Temperature table provided in t...

Page 29: ...y inlet Clearance above paved sidewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within...

Page 30: ...ve paved sidewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 12 7 feet 2 1m 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3...

Page 31: ...On roof terminations the intake piping should termi nate straight down using two 90 elbows See figure 33 4 Exhaust piping must terminate straight out or up as shown A reducer may be required on the e...

Page 32: ...ed FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION EXHAUST VENT 1 1 2 38mm accelerator provided on 71M80 44W92 kits for ML193UH045P24B 070P24B 070P36B EXHAUST VENT...

Page 33: ...227 mm Min 12 305 mm Min 16 405 mm Max 6 152 mm Max 6 152 mm Min 24 610 mm Max 9 227 mm Min 12 305 mm Min 20 508 mm Max 6 152 mm Max Intake Elbow WALL SUPPORT B A D E B D E A ALTERNATE TERMINATIONS TE...

Page 34: ...p of chimney and terminate as illus trated In any exterior portion of chimney the exhaust vent must be insulated FIGURE 43 STRAIGHT CUT OR ANGLE CUT IN DIRECTION OF ROOF SLOPE EXHAUST VENT 1 2 13mm WE...

Page 35: ...length above the condensate drain outlet connection Any length above 5 may re sult in a flooded heat exchanger if the combined pri mary drain line were to become restricted NOTE In horizontal applicat...

Page 36: ...n FurnaceCondensate DrainConnection From Evaporator Coil Optional Condensate Trap With Optional Overflow Switch FIGURE 49 ML193UH with Evaporatoir Coil Using a Separate Drain Unit shown in horizontal...

Page 37: ...ndensate drain outlet must be vented to relieve pressure in or der for the furnace pressure switch to operate properly FIGURE 51 ML193UH with Evaporator Coil Using a Common Drain Unit shown in horizon...

Page 38: ...Condensate Drain Connection In Unit Vent To Drain Condensate Drain Connection In Unit Optional Condensate Drain Connection OptionalDrainPipingFromTrap DrainTrapAssembly Furnished DrainTrap Assembly w...

Page 39: ...y for 3 4 inch Drain Pipe 90 Street Elbow 1 2 inch PVC Not Furnished Condensate Drain Connection In Unit Adapter 1 2 inch slip X 1 2 inch mpt Not Furnished Condensate Drain Connection In Unit Vent To...

Page 40: ...int the trap should be primed with suffi cient water to ensure proper condensate drain opera tion WARNING If you do not follow these instructions exactly a fire or explosion may result causing propert...

Page 41: ...al 2 cu ft DIAL 045 80 160 200 400 070 55 110 136 272 090 41 82 102 204 110 33 66 82 164 135 27 54 68 136 Natural 1000 btu cu ft LP 2500 btu cu ft Furnace should operate at least 5 minutes before chec...

Page 42: ...ural to L P propane gas changeover kit is necessary to convert this unit Refer to the changeover kit installation instruction for the conversion procedure TABLE 21 Manifold and Supply Line Pressure 0...

Page 43: ...t will be off when the system switch is in OFF position B Temperature Rise Temperature rise depends on unit input blower speed blower horsepower and static pressure as marked on the unit rating plate...

Page 44: ...equently during the winter and the indoor coil to freeze in the summer resulting in an increase in the number of service calls Before using any filter with this system check the specifications provide...

Page 45: ...ower deck Spread cabinet sides slightly to allow clearance for removal of heat exchanger 22 Remove screws along vestibule sides and bottom which secure vestibule panel and heat exchanger as sembly to...

Page 46: ...Gently clean the face of the burners using the soft brush attachment on a vacuum cleaner Visually in spect the inside of the burners and crossovers for any blockage caused by foreign matter Remove any...

Page 47: ...2 minutes or control goes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 The integrated control A92 energizes ignitor A 20 second warm up period begins...

Page 48: ...MUM OF 1 SECOND GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2...

Page 49: ...PLETE YES 4 SECONDS YES HAS CONTROL RESET IGNITION SEQUENCE FOUR TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOO...

Page 50: ...ASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR OFF THERM...

Page 51: ...ED THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G EN...

Page 52: ...oes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 The integrated control A92 energizes ignitor A 20 second warm up period begins 5 Gas valve opens for...

Page 53: ...DOOR BLOWER ON HEATING SPEED LED 1 FLASH GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 2 FLASHES Sequence holds until pressure switch opens or thermostat resets control NO...

Page 54: ...HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 7 FLASHES WATCHGUARD FAILURE CODE IS 60 MINUTE RESET PERIOD COMPLETE NO 4 SECONDS YES HAS CONTROL...

Page 55: ...AC TERM OFF WITH 60 SECOND DELAY NO NO IS VOLTAGE ABOVE 90 VOLTS LED ON STEADY CONTROL WILL CONTINUE TO CALL FOR COOLING IN THIS CONDITION YES NO IS THERE A PROPER GROUND YES NO LED ON STEADY CONTROL...

Reviews: