TABLE 3
DEMAND DEFROST CONTROL (A108) INPUTS, OUTPUTS AND CONFIGURABLE SETTINGS
Control
Locations
Control Label or
Description
Purpose
Function
P1
50, 70, 90, 100
Defrost Temperature
Termination Shunt (Jumper)
Pins
The demand defrost control (illustrated in figure 17) has selections which
are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination
pin is factory-set at 50°F (10°C). If the temperature shunt is not installed,
the default termination temperature is 90°F (32°C).
P2
W1
24VAC Thermostat Input /
Output
24VAC input / output from indoor thermostat to indoor unit.
C
24VAC Common
24VAC common.
L
Thermostat Service Light
Thermostat service light connection.
R
24VAC
24VAC.
Y2
Thermostat Input
Controls the second stage operation of the unit.
O
Thermostat Input
Reversing valve solenoid.
Y1
Thermostat Input
Controls the operation of the unit.
P3
55, 50, 45, 40
Low Ambient Thermostat
Pins
Provides selection of the Y2 compressor lock-in temperature. Valid
options are 40, 45, 50 and 55 degrees Fahrenheit.
P4
DIS-YEL
Coil Sensor
(P4-5) Ground connection for outdoor coil temperature sensor.
(P4-6) Connection for outdoor coil temperature sensor.
AMB-BLACK
Ambient Sensor
(P4-3) Ground connection for outdoor ambient temperature sensor.
(P4-4) Connection for outdoor ambient temperature sensor.
COIL-BROWN
Discharge Sensor
No discharge sensor is used; replaced by 10K resistor.
P5
DELAY
Delay Mode
The demand defrost control has a field-selectable function to reduce
occasional sounds that may occur while the unit is cycling in and out of
the defrost mode. When a jumper is installed on the DELAY pins, the
compressor will be cycled off for 30 seconds going in and out of the
defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE
-
The 30-second off cycle is NOT functional when TEST pins on
P1 are jumpered.
P6
TST, PS DF, C, R, O, Y1, Y2
Factory Test Connectors
No field use.
DS1
RED LED
Diagnostic LED
Demand defrost control LEDs may be OFF, ON, or FLASHING to
indicate diagnostic conditions which are described in table 3.
DS2
GREEN LED
FAN
TWO CONNECTORS
Condenser Fan Operation
These two connections provide power for the condenser fan.
O OUT
O OUT
24 VAC output
24 VAC output connection for reversing valve.
LO-PS
LO-PS
Low-Pressure Switch
When the low pressure switch trips, the demand defrost control will cycle
off the compressor, and the strike counter in the demand defrost control
will count one strike. The low pressure switch is ignored under the
following conditions:
during the defrost cycle and 90 seconds after the termination of
defrost
when the average ambient sensor temperature is below 0°F (-18°C)
during 90 seconds following the start of the compressor
during TEST mode.
Y2 OUT
Y2 OUT
24 VAC Output
24 VAC output for second-stage compressor solenoid.
Y1 OUT
Y1 OUT
24 VAC Common Output
24 VAC common output, switched for enabling compressor contactor.
HS-PS
HS-PS
High-Pressure Switch
When the high pressure switch trips, the demand defrost control will cycle
off the compressor, and the strike counter in the demand defrost control
will count one strike.
L
L
Service Light Output
24VAC service light output.
24V
24V
24 Volt output
24VAC typically used to supply power to the Lennox System Operation
Monitor (LSOM). Not used in this system.
Summary of Contents for ML16XP1 Series
Page 28: ...Page 28 Wiring and Sequence of Operation FIGURE 15 Typical Unit Wiring 018 thru 030 units ...
Page 29: ...Page 29 FIGURE 16 Typical Unit Wiring 036 thru 060 units ...
Page 30: ...Page 30 FIGURE 17 Typical Factory Wiring 018 thru 030 units ...
Page 31: ...Page 31 FIGURE 18 Typical Factory Wiring 036 thru 060 units ...