NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Maintain a minimum 1" (25 mm) clearance to 

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; 3" (76 mm) 

on top, 1" (25 mm) on sides, and 1" (25 mm) 

at the bottom.

B.

 

Frame exterior wall opening -

 

Locate  the  center  of  the  vent  outlet  on  the 

exterior  wall  according  to  the  dimensions 

shown  in  Figure  13  on

 

Page  10.  Cut  and/

or  frame  an  opening,  10-1/2"  x  12-1/8" 

 

(267 mm x 308 mm) inside dimensions, about 

this center. 

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 

the center above the appliance. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center (refer 

to Figure 18 on

 

Page 14).

u

 Ceiling 

Firestop / Spacer 

(SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

 

When using Secure Flex™, use Firestop / Spacer SF4.5VF

v

 

When using Secure Flex, use Firestop / Spacer SF4.5HF

V

H1

H

V1

Example:  If 20 feet total (H+H

1

horizontal vent run is needed, then  

4 feet minimum of (V) vertical vent 

will be required.

This table shows a 1(V) to 5(H) 

ratio.    For  every  1  foot  of  (V) 

vertical,  you  are  allowed  5  feet 

of  (H+H

1

)  horizontal  run  up  to 

a maximum total horizontal run 

of 20 feet.

An elbow is acceptable as 1 foot 

of  vertical  rise  except  where 

an  elbow  is  the  only  vertical 

component  in  the  system  (see 

Figure 31).

Table B

H + 

H

1

 Maximum

 

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

H + H

1

 = 20 feet (6.096 m) Max.

V + V

1

 + H + H

1

 = 60 ft. (18.3 m) Max.

Figure 27 - 

Top Vent - THREE ELBOWS

LENNOX HEARTH PRODUCTS  •  MERIT

® 

 SERIES DIRECT-VENT GAS FIREPLACES  •  MODELS MLDVT-30/35/40/45  •  INSTALLATION INSTRUCTIONS

VERTICAL VENT FIGURES/TABLES 

(continued)

HORIZONTAL (OUTSIDE WALL) 

TERMINATION SYSTEM

See  Figure  28  on

 

Page  18,  and  Figures  29 

through 34 on

 

Pages 19 through 22 and their 

associated  Horizontal Vent Table which illustrate 

the various horizontal venting configurations 

that are possible for use with these appliances.  

Secure Vent™

 pipe applications are shown in 

these  Figures; 

Secure  Flex™

  pipe  may  also 

be used. A Horizontal Vent Table summarizes 

each system’s minimum and maximum vertical 

and horizontal length values that can be used 

to design and install the vent components in a 

variety of applications. 

Both of these horizontal vent systems terminate 

through an outside wall. Building Codes limit 

or prohibit terminating in specific areas. Refer 

to Figure 7 on

 

Page 7 for location guidelines.

Secure Vent SV4.5 direct-vent system compo

-

nents are unitized concentric pipe components 

featuring positive twist lock connection, (refer 

to Figure 19 on

 

Page 14).  All of the appli-

ances covered in this document are fitted with 

collars having locking inclined channels. The 

dimpled end of the vent components fit over 

the appliance collar to create the positive twist 

lock connection.

A.

 

Plan the vent run -

 

Analyze  the  vent  routing  and  determine  the 

types  and  quantities  of  sections  required       

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" 

(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 

mm)  net  section  lengths  are  available.    It  is 

recommended that you plan the vent lengths 

so that a joint does not occur at the intersection 

of ceiling or roof joists. Make allowances for 

elbows as indicated in Figure 21.

Summary of Contents for Meris SeriesM LDVT-45NE

Page 1: ...T AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS UNE SURFACE VITR E CHAUDE PEUT CAUSER DES BR LURES LAISSER REFROIDIR LA SURFACE VITR E AVANT D Y...

Page 2: ...lation The Electronic appliances have an electronic intermittent pilot ignition system External electrical power is required to operate these units The battery back up can be used in case of a power o...

Page 3: ...lation de cet appareil These appliances comply with National Safety Standards and are tested and listed by ETL Intertek Report No 100326540PRT 001 to ANSI Z21 88 in Canada CSA 2 33 and CAN CGA 2 17 M9...

Page 4: ...jurisdiction and by the USA National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 codes latest edition Installtheapplianceaccordingtotheregulations of the local au...

Page 5: ...le etc a metal or woodbarriercoveringtheentirebottomsurface must be used Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and w...

Page 6: ...6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12 12 to 14 12 5 0 1 52 14 12 to 16 12 6 0 1 83 16 12 to 18 1...

Page 7: ...e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s...

Page 8: ...ment door Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements ShelfHeight Toprovideforthelowestpossibleshelfsurface the...

Page 9: ...eir equivalent Unit Being Secured by its Nailing Flanges to the Framing Left Side Front Corner of Fireplace Shown Right side requirements are the same NOTE The nailing flanges combustible mem bers and...

Page 10: ...Dimensions Model No A B C D MLDVT 30 in 30 1 4 35 1 4 39 1 4 16 mm 768 895 997 406 MLDVT 35 in 35 1 4 35 1 4 39 1 4 16 mm 895 895 997 406 MLDVT 40 in 40 1 4 40 1 4 44 1 4 16 mm 1022 1022 1124 406 MLD...

Page 11: ...nts outlined in the National Fuel Gas Code NFPA 54 latest edition USA or CAN CSA B149 1 latest edition Canada Also see Figure 13 Figure 15 Route Gas Line 3 76 mm Left Side Front Corner of Fireplace Fr...

Page 12: ...u foumisseunde gaz Useonlyapprovedventingcomponents See Approved Vent Components on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple appliances a...

Page 13: ...4 1 1 3 5 5 2 4 4 0 2 2 0 1 1 5 1 5 8 3 5 5 7 8 4 4 1 0 0 2 1 1 4 1 9 4 5 5 7 5 4 1 0 2 1 1 1 5 1 8 5 5 5 6 4 0 0 0 0 2 1 2 1 5 2 6 5 5 7 8 6 4 1 0 0 0 2 1 3 1 5 8 6 5 5 7 3 7 4 0 1 0 0 2 1 3 1 3 7 5...

Page 14: ...nal specifications Where required a telescopic vent section SV4 5LA may be used to provide the installer withanoptionininstallingintightand confined spaces or where the vent run made up of fixed lengt...

Page 15: ...align with the required direction of the next vent run element Twist elbow sections in a clockwise direction onlysoastoavoidthepossibilityofunlocking any of the previously connected vent sections see...

Page 16: ...all the way down to at or near level SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF S...

Page 17: ...op Vent three elbows LENNOX HEARTH PRODUCTS MERIT SERIES DIRECT VENT GAS FIREPLACES MODELS MLDVT 30 35 40 45 INSTALLATION INSTRUCTIONS VERTICAL VENT FIGURES TABLES continued Horizontal Outside Wall Te...

Page 18: ...vent run element Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any ofthepreviouslyconnectedventsections see Figure 19 on Page 14 I Continue installatio...

Page 19: ...ng the use of the fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the use of a Termination...

Page 20: ...NENT IN THE SYSTEM see Figure 31 Use Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses Figure 32 Top Vent ONE 90 DEGREE ELBOW ELBOW CONNECTION NOT DI...

Page 21: ...HEARTH PRODUCTS MERIT SERIES DIRECT VENT GAS FIREPLACES MODELS MLDVT 30 35 40 45 INSTALLATION INSTRUCTIONS See Table 8 on Page 20 as an aid in venting component selection for a particular range of ext...

Page 22: ...g Firestop Spacer SV4 5VF When using Secure FlexTM use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF See Table 8 on Page 20 as anaidinventingc...

Page 23: ...proximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptorcol lar Ensure the flexible vent pipe completely engages the adaptor collar to a d...

Page 24: ...TP TH TP IN ORANGE THTP BLACK TP GREEN TH TO WALL SWITCH OR THERMOSTAT Refer to Section A for millivolt appliances and Section B for electronic appliances The gas valve is set in place and pre wired a...

Page 25: ...itch to the OFF position 10 After the wiring is complete replace the cover plate Note No batteries to be installed in the battery holderuntilapoweroutage oriftheapplianceis to be operated solely with...

Page 26: ...ff valve and gas lex line and pull the assembly forward out of the compart ment Separate the shut off valve from the gas flex line Determine the length of pipe needed to route the gas line from the la...

Page 27: ...he pilot lighting instructions provided in the Care and Operation Instructions manual For piezo igniter location see Figure 41 on Page 26 millivolt appliances only Note Lighting Instructions are also...

Page 28: ...he rear log 1 as shown Position it on the left rear log bracket 2 Place the left front log 2 as shown Posi tion it against the left front of the log rack 3 Place the right front log 3 as shown Posi ti...

Page 29: ...35 H7666 Left Rear Log Bracket Right Rear Log Bracket Glowing Embers Do not place glowing ember over burner slots Log Rack Volcanic Stone 4 5 3 2 1 2 3 1 Position on the left rear log bracket Right Re...

Page 30: ...g bracket 4 2 3 Position the left front log 2 and the right front log 3 against the log rack 3 2 Log Number Description 1 Rear Log 2 Left Front Log 3 Right Front Log 4 Left Cross Log 5 Right Cross Log...

Page 31: ...hannel above the door Pull the door forward 4 Retrieve the glass door Visually inspect the gasket on the backside of the frame Gasket surface must be clean free of irregularities and seated firmly 5 I...

Page 32: ...HEARTH PRODUCTS MERIT SERIES DIRECT VENT GAS FIREPLACES MODELS MLDVT 30 35 40 45 INSTALLATION INSTRUCTIONS 1 Locateadjustmentrodandadjustairshutter to the standard setting as shown in Figure 50 adjust...

Page 33: ...ng flush with the finished wall position framework to accommodate the thickness of the finished wall Figure 53 See Page 5 for Cold Climate Insulation and Page 8 for Clearances Top of Appliance 3 76 mm...

Page 34: ...estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor opera la chimenea encendi ndola y apag ndola...

Page 35: ...V4 5VF 10 Firestop Spacer Vertical rigid 1 1 1 spacing 10 pack 96K92 SV4 5SP Support Plate LENNOX HEARTH PRODUCTS MERIT SERIES DIRECT VENT GAS FIREPLACES MODELS MLDVT 30 35 40 45 INSTALLATION INSTRUCT...

Page 36: ...in 190 5 mm for flex 6 pack H7748 FVK36 36 Flex Connector Kit Note Flex attaches to appliance collar at one end and to rigid venting at other end Listed Secure Vent Components Cat Model Description 1...

Page 37: ...e front glass door assembly See Figure 49 on Page 31 Step 3 Carefully remove the logs Take care not to break the logs Step 4 Refer to Figure 55 on Page 38 Remove the burner assembly with attached vent...

Page 38: ...sure regulator and diaphragm Discard allremovedcomponents Ensuretheprovided diaphragm is installed properly onto the replacement pressure regulator and install the new pressure regulator using the new...

Page 39: ...the orifice with the one provided with the kit Exercise extreme care to prevent damagetoorbreakageoftheigniterassembly All Models Step 9 Refer to Figure 55 on Page 38 and Figure 60 VERIFY THE PROPER O...

Page 40: ...time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1508 Elm Hill Pike Suite...

Reviews: