Equipment combinations 

Type of unit 

Type reference 

Data sheet 

Temperature sensor

 

QAH11.1 

1840 

Room sensor 

QAA32 

1747 

Changeover mounting kit

 

ARG86.3 

1840 

Motoric on/off actuator 

SFA21... 

4863 

Thermal actuator (for radiator valve) 

STA21... 

4893 

Thermal actuator (for small valve 2,5 mm) 

STP21... 

4878 

Mechanical design 

The unit consists of two parts: 

• 

A plastic housing which accommodates the electronics, the operating elements and 
the built-in room temperature sensor 

• 

A mounting base 

The housing engages in the mounting base and snaps on. 
The base carries the screw terminals; the DIP switches are located at the rear of the 
housing. 

3021

Z

01

2

5

6

1

3

4

 

1.  Operating mode selector 

(standby, heating or cooling mode with manual selection of fan speed) 

2  LEDs for indicating heating mode, cooling mode and fan operation 
3  Setting facility for minimum setpoint limitation  (in increments of 1 K) 
4  Setting facility for maximum setpoint limitation  (in increments of 1 K) 
5  Room temperature setpoint knob 

Set of DIP switches 

DIP switch no.  Meaning 

Position ON 

Position OFF 

Fan control 

Fan control is temperature-
dependent in all operating 
modes 

Fan control in normal operation is tem-
perature-independent 

1)

 

Operating mode change-
over via an external switch 

Changeover between normal 
operation and energy saving 
mode 

Changeover between normal operation 
and standby 

1)

 

 

Operating action of switch 
for external operating 
mode changeover 

Changeover activated when 
contact of switch is closed 
(N.O.) 

1)

 

Changeover activated when contact of 
switch is open (N.C.) 

 

Standby  

Frost protection function not 
enabled 

Frost protection function enabled 

1)

 

Switching differential 

1 K in heating mode 

1) 

0.5 K in cooing mode 

1)

 

4 K in heating mode 
2 K in cooling mode 

Setting and operating 
elements 

Legend

 

5

Summary of Contents for LXRCC20

Page 1: ...Providing indoor climate comfort Application guide LXRCC20 AGU 0509 E LXRCC20 Remote control ...

Page 2: ......

Page 3: ...ing changeover Operating modes normal energy saving and frost protection mode or OFF Operating mode changeover input for remote control Selectable control parameters Operating voltage AC 230 V Use Typical use Control of the room temperature in individual rooms that are heated or cooled with two pipe fan coil units equipped with an electrical heater For opening or closing a valve for switching an e...

Page 4: ...er must be equipped with a separate safety device thermal cutout The heating or cooling valve receives the OPEN command via control output Y11 when 1 the measured room temperature lies by half the switching differential below the setpoint heating mode or above the setpoint cooling mode and 2 the valve has been fully closed for more than one minute The heating or cooling valve receives the CLOSE co...

Page 5: ...e electrical heater has been switched on for more than one minute When two heating sequences are selected the two outputs cannot be switched ON the same time Two outputs must be switched ON seperately with at least 1 minute delay In case of set point change the two heaters are allowed to switch OFF together For this operation DIL switch no 8 must be set to ON factory setting The electrical heater ...

Page 6: ...C and the setpoint adjusted by the user will be ignored If frost protection operation is locked DIP switch no 4 in position ON standby is locked also which means that the controller will not switch to standby but to OFF In frost protection mode the electrical heater is always enabled independent of the position of DIL switch no 8 behaviour of electrical heater in cooling mode In energy saving mode...

Page 7: ...and fan operation 3 Setting facility for minimum setpoint limitation in increments of 1 K 4 Setting facility for maximum setpoint limitation in increments of 1 K 5 Room temperature setpoint knob 6 Set of DIP switches DIP switch no Meaning Position ON Position OFF 1 Fan control Fan control is temperature dependent in all operating modes Fan control in normal operation is tem perature independent 1 ...

Page 8: ...sed to direct solar radiation Mounting height is about 1 5 m above the floor The connecting wires can be run to the controller from a recessed conduit box Check the settings of the DIL switches no 1 through no 8 and change them if required It setpoint limitation is required use the minimum and maximum limitation facility en ergy saver After applying power the controller makes a reset during which ...

Page 9: ...ion at 25 C max 0 7 K Switching differential in heating mode SDH select able 1 K or 4 K Switching differential in cooling mode SDC select able 0 5 K or 2 K Dead zone Xdz in normal operation 2 K or 5 K Setpoint Energy saving mode heating 16 C Setpoint Energy saving mode cooling 28 C Setpoint Standby 8 C Operation Climatic conditions Temperature Humidity to IEC 721 3 3 class 3K5 0 50 C 95 r h Transp...

Page 10: ... operating mode changeover switch operating action can be selected Q1 Control output Fan speed I AC 230 V Q2 Control output Fan speed II AC 230 V Q3 Control output Fan speed III AC 230 V Y11 Control output Valve AC 230 V N O contact for N C valves Y12 Control output Valve AC 230 V N C contact for N O valves Y21 Control output Electric heating AC 230 V Connection diagram L L B1 M B2 D1 GND Q1 Q2 Q3...

Page 11: ......

Page 12: ...to quality the Specifications Ratings and Dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installation and service must be performed by a qualified installer and servicing agency Direct Sales Offices LENNOX DISTRIBUTION Distributors and Agents Algeria Aust...

Reviews: