The controller acquires the room temperature with its integrated sensor or external 
room temperature sensor (QAA32) or external return air temperature sensor (QAH11.1) 
– if used – and maintains the setpoint by delivering control commands to the 2-point-
valve. The switching differential can be 1 or 4 K in heating mode and 0.5 or 2 K in cool-
ing mode. 

The fan is switched to the selected speed via control output Q1, Q2 or Q3. 

When the function “Temperature-dependent fan control“ is activated (can be selected 
with DIP switch no.1), the fan is switched on / off depending on the temperature, that is, 
together with the valve. 

It is switched off by 

• 

leaving the heating or cooling sequence, provided the function “Temperature-
dependent fan control“ is activated, or 

• 

manually changing to standby  , provided plant conditions do not call for frost 
protection mode, or 

• 

activating an external operating mode changeover switch, provided plant conditions 
do not call for energy saving or frost protection mode, or  

• 

by turning the controller’s power supply off. 

To avoid overtemperatures of the electrical heater or to prevent the thermal cutout from 
responding, the fan will overrun for 30 seconds when the electrical heater is switched 
off. During that period of time, the fan LED flashes. 

In the event of failure, the RCC20 cannot protect the electric heater against overtem-
peratures. For this reason, the electric heater must be equipped with a separate safety 
device (thermal cutout). 

 

The heating or cooling valve receives the 

OPEN

 command via control output Y11 when  

1.  the measured room temperature lies by half the switching differential below the 

setpoint (heating mode) or above the setpoint (cooling mode), and 

2.  the valve has been fully closed for more than one minute. 
 
The heating or cooling valve receives the 

CLOSE 

command via control output Y11 

when 

1.  the measured room temperature lies by half the switching differential above the 

setpoint (heating mode) or below the setpoint (cooling mode), and 

2.  the valve has been fully open for more than one minute. 

Note: 

control output Y12 delivers a control command which is inverted to the 
control command at output Y11 and can be used for normally open valves 

The RCC20 provides control either depending on to the measured room temperature or 
depending on the fan coil unit’s return air temperature. Changeover is automatic if a 
QAH11.1 cable temperature sensor is used. 

The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) is 
used by the controller to switch from heating to cooling mode, or vice versa. When the 
water temperature lies above 28 °C, the controller switches to heating mode, below  
16 °C it switches to cooling mode. If, immediately after switching on, the water tempera-
ture lies between the 2 changeover points, the controller will start in heating mode. The 
water temperature is measured at minute-intervals and the operational status updated. 

Fan operation 
 

Note 

 

ON 

Heating and cooling 
mode 

.
.
.
.
.

OFF 

Return air tempera-
ture 

Automatic 
changeover 

2

Summary of Contents for LXRCC20

Page 1: ...Providing indoor climate comfort Application guide LXRCC20 AGU 0509 E LXRCC20 Remote control ...

Page 2: ......

Page 3: ...ing changeover Operating modes normal energy saving and frost protection mode or OFF Operating mode changeover input for remote control Selectable control parameters Operating voltage AC 230 V Use Typical use Control of the room temperature in individual rooms that are heated or cooled with two pipe fan coil units equipped with an electrical heater For opening or closing a valve for switching an e...

Page 4: ...er must be equipped with a separate safety device thermal cutout The heating or cooling valve receives the OPEN command via control output Y11 when 1 the measured room temperature lies by half the switching differential below the setpoint heating mode or above the setpoint cooling mode and 2 the valve has been fully closed for more than one minute The heating or cooling valve receives the CLOSE co...

Page 5: ...e electrical heater has been switched on for more than one minute When two heating sequences are selected the two outputs cannot be switched ON the same time Two outputs must be switched ON seperately with at least 1 minute delay In case of set point change the two heaters are allowed to switch OFF together For this operation DIL switch no 8 must be set to ON factory setting The electrical heater ...

Page 6: ...C and the setpoint adjusted by the user will be ignored If frost protection operation is locked DIP switch no 4 in position ON standby is locked also which means that the controller will not switch to standby but to OFF In frost protection mode the electrical heater is always enabled independent of the position of DIL switch no 8 behaviour of electrical heater in cooling mode In energy saving mode...

Page 7: ...and fan operation 3 Setting facility for minimum setpoint limitation in increments of 1 K 4 Setting facility for maximum setpoint limitation in increments of 1 K 5 Room temperature setpoint knob 6 Set of DIP switches DIP switch no Meaning Position ON Position OFF 1 Fan control Fan control is temperature dependent in all operating modes Fan control in normal operation is tem perature independent 1 ...

Page 8: ...sed to direct solar radiation Mounting height is about 1 5 m above the floor The connecting wires can be run to the controller from a recessed conduit box Check the settings of the DIL switches no 1 through no 8 and change them if required It setpoint limitation is required use the minimum and maximum limitation facility en ergy saver After applying power the controller makes a reset during which ...

Page 9: ...ion at 25 C max 0 7 K Switching differential in heating mode SDH select able 1 K or 4 K Switching differential in cooling mode SDC select able 0 5 K or 2 K Dead zone Xdz in normal operation 2 K or 5 K Setpoint Energy saving mode heating 16 C Setpoint Energy saving mode cooling 28 C Setpoint Standby 8 C Operation Climatic conditions Temperature Humidity to IEC 721 3 3 class 3K5 0 50 C 95 r h Transp...

Page 10: ... operating mode changeover switch operating action can be selected Q1 Control output Fan speed I AC 230 V Q2 Control output Fan speed II AC 230 V Q3 Control output Fan speed III AC 230 V Y11 Control output Valve AC 230 V N O contact for N C valves Y12 Control output Valve AC 230 V N C contact for N O valves Y21 Control output Electric heating AC 230 V Connection diagram L L B1 M B2 D1 GND Q1 Q2 Q3...

Page 11: ......

Page 12: ...to quality the Specifications Ratings and Dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installation and service must be performed by a qualified installer and servicing agency Direct Sales Offices LENNOX DISTRIBUTION Distributors and Agents Algeria Aust...