Page 11
Troubleshooting
Problem
Possible Causes
Dust is emitted from
either the indoor or
outdoor unit
The unit may accumulate dust during extended periods of non-use, which will be emitted when the
unit is turned on. This can be mitigated by covering the unit during long periods of inactivity.
The unit emits a bad
odor
The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which
will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.
The fan of the
outdoor unit does not
operate
During operation, the fan speed is controlled to optimize product operation.
Troubleshooting Tips
When troubles occur, please check the following points before contacting a repair company.
Problem
Possible Causes
Solution
The unit is not
working
Power failure
Wait for the power to be restored
The power switch is off
Turn on the power
The fuse is burned out
Replace the fuse
Remote control batteries are dead
Replace the remote control batteries
The unit’s 3-minute protection has been
activated
Wait three minutes after restarting the unit
Poor cooling
performance
Temperature setting may be higher than the
ambient room temperature
Lower the temperature setting
The heat exchanger on the indoor or outdoor
unit is dirty
Clean the affected heat exchanger
The air filter is dirty
Remove the filter and clean it according to instructions
The air inlet or outlet of either unit is blocked
Turn the unit off, remove the obstruction and turn it
back on
Doors and windows are open
Make sure that all doors and windows are closed while
operating the unit
Excessive heat is generated by sunlight
Close windows and curtains during periods of high
heat or bright sunshine
Low refrigerant due to leak or long-term use
Check for leaks, re-seal if necessary and top off
refrigerant
The unit starts and
stops frequently
There’s too much or too little refrigerant in the
system
Check for leaks and recharge the system with
refrigerant
There is air, incompressible gas or foreign
material in the refrigeration system.
Evacuate and recharge the system with refrigerant
System circuit is blocked
Determine which circuit is blocked and replace the
malfunctioning piece of equipment
The compressor is broken
Replace the compressor
The voltage is too high or too low
Install a manostat to regulate the voltage
Poor heating
performance
The outdoor temperature is lower than 7°C
(44.5°F)
Check for leaks and recharge the system with
refrigerant
Cold air is entering through doors and windows
Make sure that all doors and windows are closed
during use
Low refrigerant due to leak or long-term use
Check for leaks, re-seal if necessary and top off
refrigerant