Page 19
TABLE 4 581027-01
LGM/LCM092U No Reheat
Outdoor
Coil
Entering
Air Temp
CIRCUIT 1
CIRCUIT 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
252
140
269
137
75
5
F
293
143
311
139
85
5
F
335
146
354
142
95
5
F
382
148
403
144
105
5
F
434
150
454
147
115
5
F
490
153
508
150
TABLE 5 581028-01
LGM/LCM092U Reheat
Outdoor
Coil
Entering
Air Temp
Circuit 1
Circuit 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
258
140
269
136
75
5
F
301
139
308
137
85
5
F
344
141
349
139
95
5
F
392
143
398
142
105
5
F
445
145
447
144
115
5
F
504
148
501
147
TABLE 6 581029-01
LGM/LCM102U No Reheat
Outdoor
Coil
Entering
Air Temp
Circuit 1
Circuit 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
256
140
259
139
75
5
F
294
143
300
141
85
5
F
333
147
341
143
95
5
F
381
149
388
146
105
5
F
433
151
438
149
115
5
F
487
155
491
153
TABLE 7 581030-01
LGM/LCM102U Reheat
Outdoor
Coil
Entering
Air Temp
Circuit 1
Circuit 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
264
140
266
137
75
5
F
301
139
300
139
85
5
F
349
141
341
141
95
5
F
399
144
390
144
105
5
F
450
146
440
147
115
5
F
508
149
494
150
TABLE 8 581031-01
LGM/LCM120U No Reheat
Outdoor
Coil
Entering
Air Temp
Circuit 1
Circuit 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
258
132
263
131
75
5
F
296
137
302
133
85
5
F
337
139
344
135
95
5
F
383
141
389
137
105
5
F
439
142
438
140
115
5
F
490
145
494
143
TABLE 9 581032-01
LGM/LCM120U Reheat
Outdoor
Coil
Entering
Air Temp
Circuit 1
Circuit 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
272
131
255
133
75
5
F
309
135
294
135
85
5
F
350
138
335
137
95
5
F
396
139
381
139
105
5
F
452
141
430
142
115
5
F
503
144
485
145
TABLE 10 581033-01
LGM/LCM150U No Reheat
Outdoor
Coil
Entering
Air Temp
Circuit 1
Circuit 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
267
122
270
113
75
5
F
308
128
313
120
85
5
F
355
133
363
127
95
5
F
399
136
407
130
105
5
F
448
139
456
132
115
5
F
503
142
510
136
TABLE 11 581034-01
LGM/LCM150U Reheat
Outdoor
Coil
Entering
Air Temp
CIRCUIT 1
CIRCUIT 2
Dis
charge
+10 psig
Suction
+5 psig
Dis
charge
+10 psig
Suction
+5 psig
65
5
F
313
123
259
113
75
5
F
353
129
302
121
85
5
F
401
134
351
127
95
5
F
445
137
396
130
105
5
F
493
140
445
133
115
5
F
548
143
499
137