Page 4
LGM/LCM036, 048, 060, 074
Shipping and Packing List
Package 1 of 1 contains:
1- Assembled unit
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is found.
General
These instructions are intended as a general guide
and do not supersede local codes in any way.
Authorities having jurisdiction should be consulted
before installation.
The LGM units are available in several heating inputs.
The LCM cooling packaged rooftop unit is the same basic
design as the LGM unit except for the heating section.
Optional electric heat is available for LCM units. LGM and
LCM units have identical refrigerant circuits with
respective 3, 4, 5, and 6 ton cooling capacities.
Units are equipped with fin/tube condenser coils.
Units are equipped with variable speed compressors.
In addition to standard heating and cooling, hot gas
reheat units provide a dehumidifying mode of operation.
Refer to Reheat Operation section.
Availability of units and options varies by brand.
Requirements
See figure 1 for unit clearances.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent
ing of refrigerant (CFC's and HCFC's) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incar
ceration may be levied for non-compliance.
WARNING
Electric shock hazard and danger of
explosion. Can cause injury, death or
product or property damage. Turn off
gas and electrical power to unit before
performing any maintenance or
servicing operations on the unit. Follow
lighting instructions attached to unit
when putting unit back into operation
and after service or maintenance.
NOTICE
Roof Damage!
This system contains both refrigerant and oil.
Some rubber roofing material may absorb oil,
causing the rubber to swell. Bubbles in the rubber
roofing material can cause leaks. Protect the roof
surface to avoid exposure to refrigerant and oil
during service and installation. Failure to follow
this notice could result in damage to roof surface.
UNIT CLEARANCES
C
D
B
A
FIGURE 1
1Unit
Clearance
A
in.(mm)
B
in.(mm)
C
in.(mm)
D
in.(mm)
Top
Clearance
Service
Clearance
48
(1219)
36
(914)
36
(914)
36
(914)
Unob
structed
Clearance to
Combustibles
36
(914)
1
(25)
1
(25)
1
(25)
Unob
structed
Minimum Opera
tion Clearance
36
(914)
36
(914)
36
(914)
36
(914)
Unob
structed
Note - Entire perimeter of unit base requires support when elevated above
mounting surface.
1
Service Clearance
- Required for removal of serviceable parts.
Clearance to Combustibles
- Required clearance to combustible material
(gas units).
Minimum Operation Clearance
- Required clearance for proper unit
operation.