Page 14
Troubleshooting
Number
Cause
Operation
indicator
Timer
indicator
PRE-DEF
indicator
Alarm
indicator
Error
Code
1
In-outdoor unit communication checking
channel is abnormal
Quick-flash
E 1
2
Room temperature sensor checking
channel is abnormal
Quick-flash
E2
3
Evaporator sensor malfunction
Quick-flash
E3
4
Condenser sensor malfunction
E4
5
Water pump temperature sensor
E5
6
Outdoor malfunction
Quick-flash Quick-flash
E6
7
EEPROM malfunction
Quick-flash Quick-flash
E7
8
Water level alarm malfunction
E8
9
DC motor speed out of control
Quick-flash
10
Outdoor unit low pressure malfunction
Quick-flash Quick-flash
11
Auto-lifting panel communication error
Quick-flash
F0
12
Auto-lifting panel malfunction
Quick-flash
F 1
13
Auto-lifting panel is open
On
F2
14
Refrigerant leak detection system
malfunction
Quick-flash
EC
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
Quick-flash
•
Fixed-speed Type